background image

8

REC Installation Manual - REC Alpha Panels  - IEC 61215 /61730
Rev 13 - 11.22 

Ref: PM-IM-23

PANEL INSTALLATION

REC solar panels are designed for capturing solar radiation and can be installed where they conform to all local structural regulations. If installing 

REC solar panels in overhead or vertical constructions, the installer must ensure that all local building codes and regulations specific to such 

installations are correctly followed. There are different options for securing REC solar panels depending on the design of the array. 

Mounting 

hardware is not supplied by REC. 

Ensure the mounting structure can withstand anticipated wind and snow loads. 

Follow the mounting hardware 

manufacturer’s instructions and recommendations at all times.

SECURING OF PANELS

A typical installation of solar panels will be carried out with suitable rails and clamps. Other types of panel support, e.g., plates, must meet the same 

specifications. Such installations have been found to be in compliance with IEC 61215 & IEC 61730 requirements for the maximum test loads of 

+7000 Pa downwards pressure and -4000 Pa upwards pressure (+4666 Pa/-2666 Pa design loads)
Site-specific factors such as high wind or snow levels must be taken into consideration to ensure this limit is not exceeded.
When installing on mounting rails, ensure they run underneath the panel and provide support to the frame. The positioning of the rail must ensure 

that the minimum clamp grip length (fig. 1) and the central point of the fixation, e.g., the bolt, is fully within the required clamping zone as indicated 

on the following pages.
REC modules must be secured with a torque as shown in the table below (fig. 1). Clamp installation must be carried out according to the 

manufacturer’s instructions, including specific hardware and torque requirements. Ensure the clamps used are suitable for the planned installation 

and expected system design loads.

•  The grip area must not extend onto the panel glass and/or cause cell shading,
•  Avoid the application of excessive pressure to prevent frame deformation,
•  The panel must be secured, e.g., clamped, at least once in each of the four marked zones shown below (fig. 2).

Fig. 1:  Clamp specifications

Fig. 2:  Panel quarter divisions

1

2

4

3

Min. grip length

Grip depth

NOTE

•  In areas of snow build-up, panels can be subjected to forces in excess of the stated limit even when snow depth does not appear extreme, 

potentially causing damage to the panel. If the installation may be affected by this, further panel support is recommended, especially on the 

lower row of panels. For a detailed look see Annex 3 for 6-point mounting.

•  In the case of any questions regarding mounting systems, or if the mounting system to be used does not match any of the instructions shown 

in this installation manual, please contact REC for further support.

i

Specifications

Length

Grip depth

5 mm - 10 mm

Min. grip length

40 mm

Torque

12 - 25 Nm

NOTE

Panels must be installed so that the cells are not shaded as this will reduce electrical output. If partial shading is inevitable at certain times of the 

day or year, it must be kept to an absolute minimum. Remove any labels or stickers that may be on the front of the panels and ensure no residue 

is left on the glass.

i

CAUTION

There must be a minimum clearance gap of 20 mm between the uppermost part of the installation surface (e.g., rooftop) and the lowest part 

of the panel (i.e., underside of panel frame) to avoid any damage to the panel and to ensure sufficient airflow for cooling, helping to improve 

performance. 
The surface below the panels must be kept clear of any objects that may cause damage to the panel. 

Legend

Clearance Gap

Clamping zone

20-40 mm

40-60 mm

>60 mm

<20 mm

Test Load

(Design Load)

Test Load

(Design Load)

Test Load

(Design Load)

Test Load

(Design Load)

0 - 255 mm

X

+1200 Pa / -1200 Pa *

(+800 Pa / -800 Pa)

+2400 Pa / -2400 Pa

(+1600 Pa / -1600 Pa)

X

255 - 375 mm

+1800 Pa / -1800 Pa *

(+1200 Pa / -1200 Pa)

+4200 Pa / -2400 Pa

(+2800 Pa / -1600 Pa)

+5400 Pa / -2400 Pa

(+3600 Pa / -1600 Pa)

X

375 - 505 mm

+1800 Pa / -1800 Pa *

(+1200 Pa / -1200 Pa)

+6200 Pa / -4000 Pa

(+4133 Pa / -2666 Pa)

+7000 Pa / -4000 Pa

(+4666 Pa / -2666 Pa)

X

505 - 610 mm

+1200 Pa / -1200 Pa *

(+800 Pa / -800 Pa)

+3000 Pa / -2400 Pa

(+2000 Pa / -1600 Pa)

+5400 Pa / -2400 Pa

(+3600 Pa / -1600 Pa)

X

610 - 700 mm

+2400 Pa / -2400 Pa

(+1600 Pa / -1600 Pa)

+2400 Pa / -2400 Pa

(+1600 Pa / -1600 Pa)

+2400 Pa / -2400 Pa

(+1600 Pa / -1600 Pa)

X

0 - 200 mm

X

+1200 Pa / -1200 Pa *

(+800 Pa / -800 Pa)

+1600 Pa / -1600 Pa *

(+1066 Pa / -1066 Pa)

X

200 - 300 mm

X

+800 Pa / -800 Pa *

(+533 Pa / -533 Pa)

+2400 Pa / -2400 Pa

(+1600 Pa / -1600 Pa)

X

Once a module is secured in each of the 4 zones (fig. 2), additional clamps, i.e., ≥5, may be freely located on panel frame without 
affecting the warranty. Loads marked with a 

*

 were not certified as part of IEC 61215/61730 testing; these have been evaluated by 

REC’s internal testing process.

Содержание Alpha Pure Series

Страница 1: ...FOR ALL REC ALPHA SOLAR PANELS CERTIFIED ACCORDINGTO IEC 61215 IEC 61730 STANDARDS rec Alph panels Installation Manual REC Alpha Pure Series REC Alpha Pure R Series Rev 13 11 22...

Страница 2: ...ure Series panels with short rails 11 Installation of REC Alpha Pure R Series panels 12 Mounting with continous rails parallel to short side of the panel 12 Mounting REC Alpha Pure R Series panels wit...

Страница 3: ...o short side of the panel 12 Fig 7 Clamping of REC Alpha Pure R Series panels with rails parallel to long side of the panel 13 Fig 8 Clamping of REC Alpha Pure R Series panels using short rails 14 Fig...

Страница 4: ...nly qualified personnel must perform work on photovoltaic systems such as installation commissioning maintenance and repairs Be sure to follow the safety instructions for all system components Ensurin...

Страница 5: ...served during handling to avoid the risk of sparking fire hazards burns and lethal electric shocks Exercise extreme caution when wiring panels and look out for damaged or dirty cables etc Never insert...

Страница 6: ...rdegradationtothepackagingorpanelcomponents pallets and panels must be stored in a controlled environment ideally internal where it is protected from the elements e g rain dust and direct sunlight If...

Страница 7: ...age Voc and short circuit current Isc deviate from specification this may indicate a configuration fault Correct DC polarity must be observed at all times Electrical Ratings Electricalratingsarewithin...

Страница 8: ...o the manufacturer s instructions including specific hardware and torque requirements Ensure the clamps used are suitable for the planned installation and expected system design loads The grip area mu...

Страница 9: ...Pa 2400Pa 2400Pa 1600Pa 1600Pa X 255 375 mm 1800Pa 1800Pa 1200Pa 1200Pa 4200Pa 2400Pa 2800Pa 1600Pa 5400Pa 2400Pa 3600Pa 1600Pa X 375 505 mm 1800Pa 1800Pa 1200Pa 1200Pa 6200Pa 4000Pa 4133Pa 2666Pa 700...

Страница 10: ...PANELS WITH CONTINOUS RAILS PARALLEL TO LONG SIDE OF THE PANEL A continous rail or other support structure spans the complete underside of the panel Legend Clearance Gap Clamping zone 20 40 mm 40 60 m...

Страница 11: ...2400Pa 3000Pa 1600Pa X 375 505 mm 1200Pa 1200Pa 800Pa 800Pa 3000Pa 3000Pa 2000Pa 2000Pa 4200Pa 4000Pa 2800Pa 2666Pa X 505 610 mm 1200Pa 1200Pa 800Pa 800Pa 2400Pa 2400Pa 1600Pa 1600Pa 3600Pa 2400Pa 240...

Страница 12: ...800Pa 1800Pa 1200Pa 1200Pa 6200Pa 3000Pa 4133Pa 2000Pa 7000Pa 3000Pa 4666Pa 2000Pa 520 570 mm 1200Pa 1200Pa 800Pa 800Pa 3000Pa 2400Pa 2000Pa 1600Pa 5400Pa 2400Pa 3600Pa 1600Pa 570 730 mm 2400Pa 2400Pa...

Страница 13: ...other support structure spans the complete underside of the panel Legend Clearance Gap Clamping zone 20 40 mm 40 60 mm 60 mm Test Load DesignLoad Test Load DesignLoad Test Load DesignLoad 90 730 mm 1...

Страница 14: ...0Pa 800Pa 2400Pa 2400Pa 1600Pa 1600Pa 3600Pa 2400Pa 2400Pa 1600Pa 570 730 mm 1200Pa 1200Pa 800Pa 800Pa 1600Pa 1600Pa 1066Pa 1066Pa 2400Pa 2400Pa 1600Pa 1600Pa 0 200 mm X 800Pa 800Pa 533Pa 533Pa 800Pa...

Страница 15: ...apply a safety factor of 1 5 to the stated test load e g test load 5400 Pa 1 5 3600 Pa design load Part Name Material Rail 6105 T5 aluminum extrusion Bolt M6 x 25 drop inT stud kit Nut M6 flanged hex...

Страница 16: ...pport structures must be used to secure the panel The center point of each clamp and the minimum grip length must be fully located within the marked zone to be rated to the given value fig 12 Legend C...

Страница 17: ...used to secure the panel The center point of each clamp and the minimum grip length must be fully located within the marked zone to be rated to the given value fig 13 Legend Clearance Gap Clamping zo...

Страница 18: ...t side as shown in fig 12 and can be further identified by the grounding symbol stamped in the frame next to it Check all applicable requirements before beginning installation Suitable grounding clips...

Страница 19: ...coveranyfaulttraceabletothereplacedconnectors Anyothermodificationtothepanelisprohibited includingthe openingofthejunctionbox unlessexplicitlyauthorizedbyREC Doingsowillinvalidatethewarranty CABLEMANA...

Страница 20: ...ng to local guidelines and regulations By ensuring REC solar panels are disposed of correctly you will help prevent any negative impact on the environment and human health The majority of the panel co...

Страница 21: ...0 04 C The temperature coefficients stated are linear values CERTIFICATIONS IEC 61215 2016 IEC 61730 2016 UL 61730 IEC 62804 PID IEC 61701 Salt Mist IEC 62716 Ammonia Resistance ISO 11925 2 Ignitabili...

Страница 22: ...IMUM RATINGS Operational temperature 40 85 C System voltage 1000V Test load front 7000Pa 713 kg m Test load rear 3000Pa 305 kg m Series fuse rating 25A Reverse current 25A See installation manual for...

Страница 23: ...slack to prevent damage due to water level changes and wave motions ii Mounting panels Installation of REC solar panels must be in accordance with the aforementioned standard mounting instructions Th...

Страница 24: ...n MLPE device directly to the solar panel frame follow the MLPE manufacturer s instructions to ensure optimum mounting of the device and prevent any slippage during operation WheninstallinganMLPEdevic...

Страница 25: ...of the laws of the Member States relating to the making available on the market of electrical equipment designed for use within certain voltage limits The technical documentation and full compliance...

Страница 26: ...tage limits The technical documentation and full compliance with the standards listed below proves the conformity of the product with the requirements of and conformity with the Electrical Equipment S...

Страница 27: ...ddition of REC Alpha 72 Series 03 2021 6 Updated Datasheets 06 2021 7 Addition of REC Alpha Pure Series 11 2021 8 Updated Datasheets 03 2022 9 Added six point clamping and added requirement for washer...

Страница 28: ...RECSOLARPTE LTD 20TUASSOUTHAVENUE14 SINGAPORE637312 SINGAPORE Tel 6564959228 Mail post recgroup com www recgroup com...

Отзывы: