Re-Verber-Ray XTS 20-50 Скачать руководство пользователя страница 1

XTS Series - 4” Tube Heater Installation, Operation, Maintenance and Parts Manual

XTS Series - 4” Tube Heater Installation, Operation, Maintenance and Parts Manual

*

XTS Series

Table of Contents

Page

Models

Warnings

Clearances to Combustibles

Product Summary

Mechanical Instructions

Heater Requirements

Theory of Operation

Wiring Diagrams

Flowchart

Parts Listing

Series Kit Contents

Project

: _____________________________

Date

: __________________

Location

: ___________________________________________________

City

: _________________________

State

: ________

Zip

: ___________

Customer Name

: _____________________________________________

Local Representative

: _________________________________________

Contractor

: _________________________________________________

Engineer

: ___________________________________________________

Address

: ___________________________________________________

City

: _________________________

State

: _________

Zip

: ___________

Phone #

: _____________________

Serial #

: ______________________

Model #

: __________________________

Date of Installation

: _____________

Notes

: _____________________________________________________

Models 

 V.6/03

Warranty registration options:
1. Register online at www.reverberray.com/warranty.
2. Fill out this page and fax to Detroit Radiant Products Co.
3. Fill out this page and mail to Detroit Radiant Products Co.

Printed in U.S.A.

  

©

 Detroit Radiant Products Co.

21400 Hoover Rd., Warren, MI 48089

T. (586) 756-0950   F. (586) 756-2626

Form# LIOXTS-3M-3/04 (LES)

Replaces Form# LIOXTS-5M-3/03

This heater must be installed and serviced by trained gas installation and service personnel only!

Improper installation, adjustment, alteration, service or maintenance can cause property damage, injury or death.
Read the installation, operating and maintenance instructions thoroughly before installing or servicing this equipment.
Protect yourself and others by observing all safety  information.  Retain instructions for future reference.

!

WARNING:

** Model requires 5EA-Sub Accessory Package.

1

2

2

3

3

4

4

5-7

8-9

10-11

12

Qty.

Model #

Gas Type 

(circle one)

BTU's

Straight 

Length

U-Tube 

Length

Weight

Typical 

Mount 

Height

Combustion 

Chamber(s)

Radiant  

Emitter Tube

"Type" Tube Pkg 

#1

"Type" Tube 

Pkg. #2

Baffle 

Pieces

XTS 20-50

N or LP

50,000

21'-7"

13'-0"

120 #

9' - 14'

 Aluminized 

4" Hot-rolled    20-4 Alum-HRT

N/A

5

XTS 20-60

N or LP

60,000

21'-7"

13'-0"

120 #

10' - 15'

 Aluminized 

4" Hot-rolled    20-4 Alum-HRT

N/A

5

XTS 20-75

N or LP

75,000

21'-7"

13'-0"

120 #

11' - 18'

 Aluminized 

4" Hot-rolled    20-4 Alum-HRT

N/A

5

XTS 30-50

N or LP

50,000

31'-3"

**17'-10"

120 #

10' - 15'

 Aluminized 

4" Hot-rolled    30-4 Alum-HRT

N/A

4

XTS 30-60

N or LP

60,000

31'-3"

**17'-10"

160 #

11' - 18'

 Aluminized 

4" Hot-rolled    30-4 Alum-HRT

N/A

4

XTS 30-75

N or LP

75,000

31'-3"

**17'-10"

160 #

12' - 20'

 Aluminized 

4" Hot-rolled    30-4 Alum-HRT

N/A

4

XTS 30-100

N or LP

100,000

31'-3"

**17'-10"

160 #

13' - 23'

 Aluminized 

4" Hot-rolled    30-4 Alum-HRT

N/A

5

XTS 40-50

N or LP

50,000

40'-11'

22'-8"

190 #

11' - 18'

 Aluminized 

4" Hot-rolled    40-4 Alum-HRT

N/A

2

XTS 40-60

N or LP

60,000

40'-11'

22'-8"

190 #

11' - 18'

 Aluminized 

4" Hot-rolled    40-4 Alum-HRT

N/A

2

XTS 40-75

N or LP

75,000

40'-11'

22'-8"

190 #

12' - 20'

 Aluminized 

4" Hot-rolled    40-4 Alum-HRT

N/A

2

XTS 40-100

N or LP

100,000

40'-11'

22'-8"

190 #

13' - 23'

 Aluminized 

4" Hot-rolled    40-4 Alum-HRT

N/A

4

XTS 40-125

N or LP

125,000

40'-11'

22'-8"

190 #

14' - 25'

 Aluminized 

4" Hot-rolled    40-4 Alum-HRT

N/A

4

XTS 40-150

N or LP

150,000

40'-11'

22'-8"

190 #

15' - 27'

 Titan/Alum

4" Hot-rolled    40-4 Ti-Al-HRT

N/A

4

XTS 50-100

N or LP

100,000

50'-7'

**27'-6"

235 #

15' - 27'

 Aluminized 

4" Hot-rolled    40-4 Alum-HRT

 10-4-HRT

2

XTS 50-125

N or LP

125,000

50'-7'

**27'-6"

235 #

15' - 27'

 Aluminized 

4" Hot-rolled    40-4 Alum-HRT

 10-4-HRT

4

XTS 50-150

N or LP

150,000

50'-7'

**27'-6"

235 #

16' - 30'

 Titan/Alum

4" Hot-rolled    40-4 Ti-Al-HRT

 10-4-HRT

4

XTS 50-175

N or LP

175,000

50'-7'

**27'-6"

235 #

17' - 35'

 Titan/Alum

4" Hot-rolled    40-4 Ti-Al-HRT

 10-4-HRT

2

XTS 50-200

N or LP

200,000

50'-7"

**27'-6"

235#

18' - 40'

 Titan/Alum

4" Hot-rolled    40-4 Ti-Al-HRT

 10-4-HRT

2

XTS 60-125

N or LP

125,000

60'-3'

32'-4"

265 #

16' - 30'

 Aluminized 

4" Hot-rolled    40-4 Alum-HRT

 20-4-HRT

2

XTS 60-150

N or LP

150,000

60'-3'

32'-4"

265 #

17' - 35'

 Titan/Alum

4" Hot-rolled    40-4 Ti-Al-HRT

 20-4-HRT

2

XTS 60-175

N or LP

175,000

60'-3'

32'-4"

265 #

17' - 35'

 Titan/Alum

4" Hot-rolled    40-4 Ti-Al-HRT

 20-4-HRT

2

XTS 60-200

N or LP

200,000

60'-3'

32'-4"

265 #

18' - 40'

 Titan/Alum

4" Hot-rolled    40-4 Ti-Al-HRT

 20-4-HRT

2

*

For complete installation instructions, see Generic IOM this piece was inserted within.  Also available at www.reverberray.com.

Содержание XTS 20-50

Страница 1: ...Typical Mount Height Combustion Chamber s Radiant Emitter Tube Type Tube Pkg 1 Type Tube Pkg 2 Baffle Pieces XTS 20 50 N or LP 50 000 21 7 13 0 120 9 14 Aluminized 4 Hot rolled 20 4 Alum HRT N A 5 XT...

Страница 2: ...used for the storage of combustible materials signs must be posted to specify the maximum permissible stacking height to maintain the required clearances from the heater to the combustibles Signs must...

Страница 3: ...ing the first tube section See Tube Installation Sequence chart at the bottom of this page for an illustration Do not use the hot rolled steel radiant tubing as the first tube combustion chamber Note...

Страница 4: ...sidewall caps for roof venting and do not use roof caps for sidewall venting Starting Circuit When voltage is applied to L1 and L2 see diagram on right a circuit is completed from L1 via the blower m...

Страница 5: ...5 Internal Wiring Diagrams Standard Wiring If any of the original wire as supplied with the appliance must be replaced it must be replaced with wiring material having a temperature rating of at least...

Страница 6: ...S SUFFICIENT TO OPERATE 10 APPLIANCES 24v EXTERNAL TRANSFORMER 24v DIGITAL T STAT COMMON REQUIRED FOR THEMOSTATS THAT REQUIRE CONSTANT POWER W L2 L1 C R COMMON 120 V Observe Polarity PANEL GROUND PANE...

Страница 7: ...MINAL 24V BK BK A B C D BR BK BK BLOWER W L1 120VAC L2 2 C GAS VALVE NO OFF P 3 LIGHTS INDICATOR M 1 3 1 2 C P M W BK W R LLWT23 MARK 17DU 117 MODULE IGNITION GND NEUT VALVE NEUT TH LINE1 SIC1 PROBE G...

Страница 8: ...of the switch Be sure to reinstall the cover Does the ignitor glow red YES Replace the pressure switch after verifying the following Baffle s is in the tube s farthest from the burner Heater fan blowe...

Страница 9: ...y correct YES With voltmeter check DC voltage at flame rod Is it greater than 30 Volts DC YES Check to make sure flame sensor wire is OK and then replace circuit board NO Sensing rod is faulty or flam...

Страница 10: ...31B 68A 352A 351A 1304 55A 5 217 202 17 218 401 NOPS 1 19B 106 12 E m i t t e r T u b e s C o m b u s t i o n C h a m b e r 21B 222 221 11 220 26A 26B 65I 26C 20C 82 XTS Series V 6 03 10 Parts Breakdo...

Страница 11: ...MP TP 26B 10 FT TITANIUM COMBUSTION TUBE TP 221 GLO BAR HOLDER GASKET TP 26C 10FT UNCOATED HOT ROLLED RADIANT TUBE TP 222 FLAME ROD TP 31B CONTROL BOX BRACKET TP 223 GAS MANIFOLD TP 33B 1 2 GAS COCK T...

Страница 12: ...P 105 Refl Endcaps 2 2 2 2 2 N A TP 106 Refl Endcap Clips 8 8 8 8 8 N A IOM Install Op Manual 1 1 1 1 1 N A XTS SERIES KIT CONTENTS AND PRODUCT FEATURES Product Features APPROVALS IAS CSA AGA Commerci...

Отзывы: