Resa integrazione invernale massima in base alla differenza di 

temperatura tra aria in ingresso alla macchina e temperatura 

dell’acqua.

ON WINTER

Maximum sensible heating capacity according to the temperature 

difference between inflow air into the unit and water.

PERDITA DI CARICO CIRCUITO IDRAULICO

PRESSURE LOSS OF THE HYDRAULIC CIRCUIT

Содержание DA 1001

Страница 1: ...rHandlingUnits UnitàTrattamento Aria DA 1001 TECHNICAL INSTALLATIONMANUAL MANUALETECNICO INSTALLAZIONE Dehumidifierhorizontalceilingmounted CommercialUnits Terziario Deumidificatore orizzontale a soffito ...

Страница 2: ......

Страница 3: ...o di Assistenza autorizzato dal Costruttore Alla fine dell installazione smaltire gli imballi secondo quanto previsto dalle normative in vigore nel Paese di utilizzo Esigere solo ricambi originali la mancata osservazione di questa norma fa decadere la garanzia SAFETY WARNINGS Readthismanualcarefullybeforeinstallingand orusingthe equipment and keep it in an accessible place This equipment constitut...

Страница 4: ...rodotto da parte dell utente comporta l applicazione delle sanzioni previste dalla vigente normativa in materia The manufacturer declines all responsibility and considers the warranty invalid in the following cases Theaforementionedwarningsandsafetyregulations including those in force in the country of installation are not respected The information given in this manual is disregarded Thereisdamage...

Страница 5: ...circuiti idronici 19 Testing Collaudo 21 Flow water setting Taratura portate acqua 21 Fan speed setting Taratura della velocità dei ventilatori 22 Summer functioning Funzionamento estivo 23 Winter functioning Funzionamento invernale 23 Distribution example Esempio di distribuzione 24 MAINTENANCE MANUTENZIONE 25 1 Ordinary maintenance 1 Manutenzione ordinaria 25 2 Extraordinary maintenance 2 Manute...

Страница 6: ...iclaggio alle aziende preposte allo scopo e ridurne così l impatto ambientale The unit packaging must be removed with care ensuring that the machine is not damaged The materials which make up the packaging are different wood cardboard nylon etc Store them separately and deliver them for disposal or where appropriate recycling to the relevant companies thus reducing the environmental impact TESTING...

Страница 7: ...ne integrazione potenza sensibile estiva e invernale acomando Iltelaiodellamacchina inlamierazincata contiene il gruppo di batterie alettate per il trattamento dell aria il circuito frigorifero per la deumidificazione il filtro dell aria per l aspirazione la vaschetta raccogli condensa il ventilatore di mandata ad alta efficienza e il quadro elettrico di comando e gestione L unitàèdotatadidisplayc...

Страница 8: ...a 6 Condensing coil Batteria condensante 7 Evaporation thermostatic valve Valvola evaporante termostatica 8 Modulating hydraulic circuit condensation valve Valvola modulante circuito idraulico condensatore 9 Tank coil Batteria serbatoio 10 Tank fill valve Valvola di carico serbatorio 11 Tank drain valve Valvola di scarico serbatoio 12 Fan Ventilatore Circuits of the unit Circuiti machina DA 1001 1...

Страница 9: ...uccessivi Icontrollidisicurezzavengonoeffettuatidallacentralinatramite i valori rilevati dalle sonde Sonda temperatura acqua pre trattamento Sonda temperatura evaporatore Sonda surriscaldamento Trasduttore di pressione Sonda temperatura vano ventilatore INTERNAL COMPONENTS DESCRIPTION COMPONENTS Components Component Description Compressor Rotative Pre treatment water sensor NTC sensor to detect th...

Страница 10: ...alificato Durante tutte le procedure di installazione assicurarsi che l apparecchiatura non sia collegata alla rete elettrica L installazionedeveessereeffettuatasoloall interno degli edifici INSTALLATION INSTALLAZIONE 1 POSITIONING AND FIXING TO THE CEILING POSIZIONAMENTO E FISSAGGIO A SOFFITTO MAX 95 MAX 30 C OK min 5 cm m i n 4 0 c m Positioning indications Indicazioni di posizionamento Minimum ...

Страница 11: ...11 mm ø8mm 2 476 811 1 Fixing to ceiling Fissaggio a soffitto min 40 cm min 20 cm min 60 cm X X Trap door Botola d ispezione 3 Washer Rondella Rubber mounts Gommino antivibrante ...

Страница 12: ...am 3 4 F con detentore di regolazione portata C Condenser water outlet 1 2 F Uscita acqua condensatore 1 2 F D Condenser water inlet 1 2 F with flow rate adjustment lockshield valve Ingresso acqua condensatore 1 2 F con detentore di regolazione portata E ø20mmcondensationrubberdrain RDZkitcondensation drain Scarico in gomma ø20 mm per condensa kit scarico condensa RDZ E B C A A B C D D E 1 2 Scari...

Страница 13: ...heck thatnotonlytheconnectionsbutalsothemachinehydraulic circuit are watertight as these could be damaged during transportation or on site during installation on this topic themanufacturerwillonlyberesponsibleforfactorydefects on the dehumidifier and under no circumstances accepts responsibility for indirect damage Thecondensationdrainandtheinletandoutletpipes must comply with the standards and la...

Страница 14: ...nstalled in the pre treatment line only and should not interfere with the post treatment line WIRINGDIAGRAMFORCOMPLETEHYDRAULICCONNECTION SCHEMA DI COLLEGAMENTO IDRAULICO COMPLETO SCHEMA IDRAULICO CON VALVOLA MODULANTE HYDRAULIC DIAGRAM WITH MODULATING VALVE IN B OUT A IN D E OUT C Tank Accumulo Drain Scarico DA 1001 PRE COND AB A B Kv 2 7 KEY LEGENDA Circulation pump Circolatore Flow rate lockshi...

Страница 15: ...onamento deve avvenire entro i valori sopra citati in caso contrario la garanzia viene a decadere immediatamente e ci sono rischi elettrici per le persone e il prodotto APERTURA SPORTELLO Thedehumidifiermustbeconnectedtoadisconnected earthedpowersocket Theelectricalsystemmustbeprotected against overloads short circuits and direct and indirect contactsandcomplywiththelawsandregulationsinforcein the...

Страница 16: ...cable phase F neutral N earth The terminal of the tension line is provided with 16 A fuse if the unit does not start even though it is energized check this fuse CONSENSI DELL UNITÀ UNIT CONSENTS L N Consenso integrazione Integration consent 1 2 3 4 7 6 8 0 5 9 10 Stagione Estate Inverno Season Summer Winter Consenso deumidificazione Dehumidification consent Consenso ricircolo Recirculation consent...

Страница 17: ...andoèattivaquestafunzionalitàdidefaultpartelamodalità ricircolo a meno che non venga chiuso il contatto rinnovo USCITA ALLARME Il relé di allarme è normalmente aperto in caso di anomalia il contatto si chiude E possibile rendere il contatto normalmente chiuso togliendo il ponticello denominato NC NO sul circuito stampato della scheda Information about the main electrical connections which must be ...

Страница 18: ...ESSIONE MODBUS MODBUS CONNECTION A TX RX B TX RX B A e non utilizzati and not used serial card 1 A B serial card 1 WI SA Serie Design Unità 1 Unità 2 Unit 1 Unit 2 UNIT MODBUS ADDRESS INDIRIZZO MODBUS MACCHINA ...

Страница 19: ...emperature inferiori ai 5 C per evitare il pericolo di ghiacciamento CARICAMENTO BATTERIA PRE TRATTAMENTO 1 Totaly open Totalmente aperto Max speed Velocità massima 2 3 Open until water flows Aperto finché non esce acqua FILLING OF THE HYDRONIC CIRCUITS Water filling in DA 1001 dehumidifiers is very important since the presence of air bubbles inside the finned coils and or in the plate exchanger c...

Страница 20: ...F ON OFF ON OFF INTEGRATION INTEGRAZ 1 Totaly open Totalmente aperto Max speed Velocità massima 2 4 3 Open until water flows Aperto finché non esce acqua CARICAMENTO CONDENSATORE A PIASTRE CARICAMENTO PRE TRATTAMENTO CON VALVOLA MODULANTE WATER FILLING FOR PLATE CONDENSER WATER FILLING FOR PRE TREATMENT COIL WITH MODULATING VALVE ...

Страница 21: ...umidity value this test is not valid with temperature values inferior to 26 C Check the temperature detected by the flow sensor Incaseof highhumidity 26 C65 RHor28 C60 RH theoutlet temperatureshouldbeabout17 C whileincaseoflowerhumidity the detected flow temperature should be approximately 16 C The test can be performed more accurately if SR 1001 unit is used and it works in fresh air ventilation ...

Страница 22: ...re the required flow Low flow rate values will cause malfunctioning in the DA1001unit thusactivatingalarmsblockingtheunit with manual reset SET VENTILATORE IMMISSIONE IN RICIRCOLO Non scendere a portate inferiori a 800 mc h d aria in quantol unitàDA1001potrebbeattivareallarmiconblocco macchina a riarmo manuale Non salire a portate superiori a 1200 mc h d aria in quanto si creano problemi di scaric...

Страница 23: ... Integrazione La Deumidificazione entra in funzione quando viene chiuso il contatto di deumidificazione vedere cap 3 Collegamenti elettrici L unità inizierà a deumidificare mantenendo una temperatura di uscita neutra rispetto a quella in ingresso La temperatura è impostata a 26 C ed è comunque modificabile da parametro vedere cap Centralina L Integrazioneentrainfunzionequandovienechiusoilcontatto ...

Страница 24: ...24 ESEMPIO DI DISTRIBUZIONE DISTRIBUTION EXAMPLE ...

Страница 25: ...pposite pannellature fissandole con le viti di serraggio All the extraordinary maintenance operations described in this chapter MUST ALWAYS BE CARRIED OUT BY QUALIFIED PERSONNEL Before performing any intervention on the unit or before accessing internal parts ensure that the electrical power supply has been disconnected There are moving components inside the unit Take particularcarewhenoperatingin...

Страница 26: ... motor it is not necessary to remove the fan Per la sostituzione del conden satore elettrico del ventilatore si trova a fianco del motore non è necessario rimuovere il ventilatore OFF Spento Remove the two screws and bracket highlighted 4 holding the fan housing then lift slightly and remove it from the machine Rimuovere infine le due viti e la staffa evidenziata 4 che blocca no il corpo ventilato...

Страница 27: ...scription Descrizione Indicates SUMMER season as active Indica la stagione ESTATE attiva Indicates WINTER season as active Indica la stagione INVERNO attiva Not used Non usato It means that the compressor operates if it flashes it means that the fan is going to start e g at the beginning or in case of defrosting Indica il compressore attivato se lampeggia è in attesa di attivarsi ad esempio all av...

Страница 28: ...n Descrizione Exitmenus listofparametersandparametervalue without saving the value and go back to the previous level Si ottiene l uscita da menù da elenco parametri da valore parametro senza salvataggio valore e ritorno a livello precedente Not used Non utilizzato Scrolling the folders and parameters display upwards Parameter value increase if in parameter value modification mode Scorrimento verso...

Страница 29: ...re 10 H2Ov Menu parameters modulating valve H2 0 pretreatment MenuparametrivalvolaH2 0modulantepretrattamento 11 bvS Not used Non utilizzato 12 inFo General reading menu Menu letture generali 13 PAr1 Access is not allowed Non accessibile H2O MENU It can be set via this menu the following operating parameters of the modulating valve MENU H2O E possibile impostare tramite questo menu i seguenti para...

Страница 30: ...rcentuale del voltaggio corrente della valvola modulante condensazione 12 7 H2Op Percentage value of the current voltage of the modulating pretreatment valve Valore in percentuale del voltaggio corrente della valvola modulante pretrattamento 12 8 Ueli Percentage value of the speed inlet fan Valore percentuale in utilizzo del set velocità ventilatore immissione 12 9 UEle Percentage value of the spe...

Страница 31: ...ase the signal is continuous it is necessary to cut off the tension to the controller for resetting Intervento del pressostato di massima pressione refrigerante In tale caso la segnalazione è persistente per cui è necessario togliere l alimentazione al controllore per permettere il reset 3 Damage on the temperature sensor of the evaporator Guasto alla sonda di temperatura evaporatore 4 Alarm disch...

Страница 32: ...y DA DA SR Prevalenza disponibile Solo DA DA SR Pa 390 301 Pre cooling water flow rate Portata acqua pre raffreddamento l h 1000 Pre cooling water outlets Attacchi acqua pre raffreddamento 3 4 F Condensation water flow rate Portata acqua condensazione l h 130 Condensation water outlets Attacchi acqua condensazione 1 2 F Pre cooling water head loss Only DA DA Modulating Valve Perdita di carico acqu...

Страница 33: ...il normale funzionamento né tantomeno l affidabilità e l integrità delle unità per applicazioni particolari contattare l ufficio tecnico del Costruttore Thegraphsshownbelowdescribetheoperatingrangeoftheunit The maximum permitted temperature of the water for operation in summer mode is 18 C Above 30 C the compressor is excluded leaving only the fan running Between30and55 Citispossibletoactivatethev...

Страница 34: ...Resa in deumidificazione e integrazione in funzione della temperatura in ingresso all unità umidità relativa ON SUMMER Performance in dehumidification mode according to the temperature relative humidity and temperature of the chilled water DA SR 1001 Performance in dehumidification integration mode DA SR 1001 Resa in deumidificazione integrazione Inlet air Aria in ingresso Outlet air Aria in uscit...

Страница 35: ...a acqua l h Head loss kPa Perdita di carico kPa Pretrattamento Pretrattamento valvola modulante INVERNALI Resa integrazione invernale massima in base alla differenza di temperatura tra aria in ingresso alla macchina e temperatura dell acqua ON WINTER Maximumsensibleheatingcapacityaccordingtothetemperature difference between inflow air into the unit and water PERDITA DI CARICO CIRCUITO IDRAULICO PR...

Страница 36: ...procedere con l accoppiamento SR PRESSURES DROP Pressure drop value in SR units which should be subtracted from the aeraulic performance of the DA units in case of combination into UC units PREVALENZE UTILI ALLA BOCCHETTA DI IMMISSIONE AVAILABLE PRESSURES TO THE INTAKE OUTLET Air flow rate m3 h Portata aria m3 h Performance Pa Prevalenza utile Pa 0 100 200 300 400 500 500 1000 1500 2000 2500 3000 ...

Страница 37: ...RED ROSSO Y out WHITE BIANCO BLACK NERO SONDATEMP CANALE DI MANDATA CONSENSI CONSENTS 0 11 12 18 0 0 19 0 0 16 0 17 22 13 0 0 24 23 N L N L N L 0V 10V REGOLATORE ELETTRONICO ELECTRONIC REGULATOR ORANGE ARANCIONE SIGN 0 10V INLET FAN REC SIGN 0 10VVENT MANDATA REC GND GND SIGN 0 10V EXPULSION FAN REC SIGN 0 10VVENT ESPULSIONE REC 9 8 7 6 AI9 AO6 DI6 DI7 DI8 DI9 COM 5 4 3 2 1 12 11 10 GND AI7 AI8 0 ...