USER MANUAL
MANUALE D’USO
HD 6045EN
-
HORN SPEAKER IN COMPLIANCE
WITH EN 54-24 STANDARD
DIFFUSORE ACUSTICO A
TROMBA CONFORME ALLA NORMA EN 54-24
Страница 1: ...USER MANUAL MANUALE D USO HD 6045EN HORN SPEAKER IN COMPLIANCE WITH EN 54 24 STANDARD DIFFUSORE ACUSTICO A TROMBA CONFORME ALLA NORMA EN 54 24 ...
Страница 2: ...f the following occur The speaker does not function or works in an anomalous way Its cable has been damaged Objects or liquids have got into the unit The speaker has been damaged due to heavy impacts or fire 7 Should the speaker emit any strange odours or smoke remove it from the line after having immediately switched the amplifier off 8 Do not connect this product to any equipment or accessories ...
Страница 3: ...phase is to be respected speakers shall be connected respecting the amplifier polarity This is important when speakers are installed adjacent one another for instance in the same room 13 To prevent inductive effects from causing hum noise and a bad system working speaker lines should not be laid together with other electric cables mains microphone or line level signal cables connected to amplifier...
Страница 4: ...use that prevents damage to the audio line due to heat on the speaker Steel bracket HD 6045EN horn loudspeakers can be easily aimed and used in sounds systems having large spaces for instance car parks football stadiums undergrounds factories warehouses etc and also in all environments that need high efficiency loudspeakers RCF S P A THANKS YOU FOR PURCHASING THIS PRODUCT WHICH HAS BEEN DESIGNED T...
Страница 5: ...ed and experienced personnel having the technical know how or sufficient specific instructions to ensure that are made correctly and prevent any electrical danger To prevent any risk of electric shock do not connect speakers when the amplifier is switched on Before turning the system on check all connections and make sure there are no accidental short circuits The entire sound system shall be desi...
Страница 6: ...speaker with suitable wall plugs having screws bolts passing through the ø 12 5 mm holes on its mounting bracket Aim the horn speaker to the listening area and fix its position by tightening the two bolts of its mounting bracket THERMAL FUSE CABLE CLAMP FIRE RETARDANT CABLE RCF CV210 CV215 CV225 NEXT SPEAKER PREVIOUS SPEAKER 0 COM 100 V 100 70 V 0 ...
Страница 7: ...he total speaker power In sound systems for emergency purposes Voice Alarm systems only use fire retardant cables i e RCF CV210 CV215 or CV225 Speaker lines must be kept separated from mains cable microphone cables or others in order to avoid inductive phenomena may cause hum or noises Use speaker cables having twisted wires to reduce hum caused by inductive effects due to coupling with electromag...
Страница 8: ...0 h 50 v fiberglass white 620 mm w 475 mm h 564 mm d 24 41 w 18 70 h 22 21 d 21 4 kg 46 4 lbs 23 6 kg 51 1 lbs 620 mm 24 41 564 mm 22 21 475 mm 18 70 1 Sensitivity is measured in full space free field with pink noise signal band limited 100 Hz 10 kHz without any equalization 1 W power 7 1 V on 50 Ω at 1 m distance 2 Max SPL average is measured as 1 but with 200 W power 100 V on 50 Ω maximum peak S...
Страница 9: ...liant with EN 54 24 2008 one of the above equalization corrections shall be applied EQUALIZATION 5 6 Freq Hz Level dB 100 30 125 11 160 3 200 0 250 1 315 0 400 1 500 2 630 4 800 6 1000 9 1250 10 1600 9 2000 8 2500 6 3150 2 4000 3 5000 6 6300 7 8000 2 10000 11 Freq Hz Level dB BW Q 1200 10 1BW 1 414 6100 10 1BW 1 414 2500 6 1BW 1 414 ...
Страница 10: ...rmany tel 49 2203 925370 e mail germany rcf it RCF Spain tel 34 91 817 42 66 e mail info rcfaudio es RCF Belgium tel 32 0 3 3268104 e mail belgium rcf it RCF USA Inc tel 1 603 926 4604 e mail info rcf usa com Except possible errors and omissions RCF S p A reserves the right to make modifications without prior notice Salvo eventuali errori ed omissioni RCF S p A si riserva il diritto di apportare m...