SPECTRUM FINNED COPPER
GAS BOILERS (MODEL SB) & 

WATER HEATERS (MODEL SW)

INSTALLATION & OPERATION MANUAL

DESIGNED AND TESTED ACCORDING TO A.S.M.E. BOILER AND PRESSURE 
VESSEL CODE, SECTION IV FOR A MAXIMUM ALLOWABLE WORKING PRESSURE 
OF 160 PSI, 

1103 kPa

 WATER

INSTALLER, THESE INSTRUCTIONS TO BE AFFIXED ADJACENT TO THE HEATER.

CONSUMER, RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE PURPOSES.

260 North Elm Street 

 

 7555 

Tranmere 

Drive

Westfi eld, MA 01085 

 

 

Mississauga, Ontario L5S 1L4 

Phone: (413) 568-9571

 

 

Phone: (905) 670-5888

Fax: (413) 568-9613 

Fax: (905) 670-5782

WARNING: If the information in this manual is not followed exactly, a fire 
or explosion may result causing property damage, personal injury or loss of life.

Do not store or use gasoline or other fl ammable vapors and liquids in the vicinity of 
this or any other appliance.

WHAT TO DO IF YOU SMELL GAS:
•  Do not try to light any appliance.
•  Do not touch any electrical switch; do not use any phone in your building.
•  Immediately call your gas supplier from a neighbor’s phone. Follow the gas 

supplier’s instructions.

•  If you cannot reach your gas supplier, call the fi re department.
Installation and service must be performed by a qualifi ed installer, service agency or 
the gas supplier.

WARNING: Failure to properly vent this unit can cause excessive amounts of carbon 
monoxide resulting in severe personal injury or death!

Содержание SPECTRUM Series

Страница 1: ...tion in this manual is not followed exactly a fire or explosion may result causing property damage personal injury or loss of life Do not store or use gasoline or other flammable vapors and liquids in...

Страница 2: ...ter To obtain the safe dependable efficient operation and long life for which this heating boiler water heater was designed these instructions must be read understood and followed The Spectrum finned...

Страница 3: ...will support the weight of the boiler water heater NOTE The Spectrum may be installed directly on combustible flooring only if RBI supplied special floor pan is used but never on carpeting see Table 2...

Страница 4: ...n 3 in 76 mm from the top of the enclosure The bottom opening must be within 12 in 305 mm of but not less than 3 in 76 mm from the bottom of the enclosure Where directly communicating with the outdoor...

Страница 5: ...onry chimney must be performed to ensure that the chimney is clean properly constructed lined and sized Exterior masonry chimneys should not be used unless properly lined to prevent condensation and d...

Страница 6: ...ef opening after 5 minutes of main burner operation Use the flame of a match or candle or smoke from a cigarette cigar or pipe Faire fonctionner le br leur principal pendant 5 min ensuite d terminer s...

Страница 7: ...INSTALLATION AND OPERATING INSTRUCTIONS Page 7 Figure 1 Vertical Venting with a Metal Chimney System and Inside Air Figure 2 Vertical Venting using a Masonry Chimney and Inside Air 10 FT 3 1m RIOM 51...

Страница 8: ...flow rates seeTable 7 or 8 Return water temperatures below 110 F 43 C will result in heat exchanger damage from excessive condensation voiding the manufacturer s warranty see Primary Secondary Piping...

Страница 9: ...em An expansion tank must be installed close to the boiler on the suction side of the system pump Primary Secondary Piping Boilers connected to heating systems using zone valves zone pumps or systems...

Страница 10: ...Drop T 30 F T 16 7 C Note Unit equipped with 4 pass headers see Table 8 Flow Rate 100 150 200 250 300 350 400 16 4 24 6 32 4 40 5 49 8 0 34 0 94 1 92 3 46 5 89 1 0 1 6 2 0 2 6 3 1 1 0 2 8 5 7 10 2 17...

Страница 11: ...atic 3 way valve design flow requirements 3 Boiler circuit piping must be sized large enough to handle maximum flow through unit 4 All boilers furnished with factory mounted outlet water temperature g...

Страница 12: ...ied 5 Secondary loop pipe diameter must be sized large enough to handle maximum flow through all units Notice These drawings show suggested piping configuration and valving Check with local codes and...

Страница 13: ...oiler is connected to a heating coil that may be exposed to refrigerated air from an air handling device the piping system must be equipped with flow control valves or some other automatic means of pr...

Страница 14: ...xchanger The cupro nickel heat exchanger allows for 100 GPM 6 3 L s 2 pass heat exchanger and 50 GPM 3 2 L s 4 pass heat exchanger SeeTable 9B Cold Water Supply The cold water supply must be piped to...

Страница 15: ...SPECTRUM INSTALLATION AND OPERATING INSTRUCTIONS Page 15 Table 9B Spectrum Pumping Performance Requirement Table Table 9A Spectrum Heat Exchanger Selection Graph...

Страница 16: ...n 6 Common piping must be sized for maximum combined heater flow 7 Hot water tanks should be equipped with a combination temperature pressure relief valve 8 MA Code requires an 1 8 hole in check valve...

Страница 17: ...90 1650 2700 4700 9700 Maximum gas volume of pipe ft3 hr Pipe length in feet Table 10 Gas Pipe Capacity Nominal Iron Pipe Size in Maximum pipe capacity in ft3 hr based on 0 60 specific gravity gas at...

Страница 18: ...alled to prevent increase creep of gas pressure when the units are not operating This pressure regulator supplied by others may be installed at the service entrance to each unit or a master regulator...

Страница 19: ...water pump is used adjust to maintain a minimum 12 psig 82 7 kPa system pressure Open the system bleed and drain valves one at a time to purge the air trapped in the heating system piping With the boi...

Страница 20: ...kwise to PILOT 9 Push in control knob all the way and hold in Immediately light the pilot with a match Continue to hold the control knob in for about one 1 minute after the pilot is lit Re lease knob...

Страница 21: ...el 6 Push in gas control knob slightly and turn clockwise to OFF 7 Wait five 5 minutes to clear out any gas Then smell for gas including near the floor If you smell gas STOP Follow B in the safety inf...

Страница 22: ...than 5 adjust it according to steps 1 through 4 Input Rate Natural Gas Gas appliances are rated based on sea level operation with no adjustment required at elevations up to 2000 ft 610 m At elevations...

Страница 23: ...n r glage une r paration ou un entretien non comforme aux normes peut entra ner des dommages mat riels des blessures exposition des mati res dangereuses ou la mort L installation et l entretien doiven...

Страница 24: ...dication of low water flow through the system 2 A damaged heat exchanger must be replaced and the condition that caused the damage resolved before the boiler water heater is returned to service Vent S...

Страница 25: ...SPECTRUM INSTALLATION AND OPERATING INSTRUCTIONS Page 25 Figure 14 Replacement Parts 4 21 1 22 26 27 6 28 25 15 16 24 12 4 3 10 8 20 2 5 36 35 31 19 18 9 7 17 11 23 30 37 34 33 32 14 13...

Страница 26: ...1244 1 70 1245 1 70 1246 1 Combustion Chamber Rear Panel 03 0886 1 03 0887 1 03 0888 1 03 0889 1 03 0890 1 03 0891 1 03 0892 1 Combustion Chamber Front Panel 03 0894 1 03 0895 1 03 0896 1 03 0897 1 0...

Страница 27: ...1332 1 70 1333 1 Burner Drawer Assembly LP Continuous Pilot 70 1334 1 70 1335 1 70 1336 1 70 1337 1 70 1338 1 70 1339 1 70 1340 1 Burner Drawer Assembly NG Intermittent Pilot 70 1355 1 70 1356 1 70 1...

Страница 28: ...e Panel 03 0774 1 1 1 1 1 1 1 12 Jacket Right Side Panel 03 0775 1 1 1 1 1 1 1 13 Jacket Front Panel 03 0767 1 03 0768 1 03 0769 1 03 0770 1 03 0771 1 03 0772 1 03 0773 1 14 Jacket Upper Front Panel 0...

Страница 29: ...16 16 16 16 16 16 NS Nut Inlet Outlet Return Headers 57 0492 12 12 12 12 12 12 12 NS Stud Inlet Outlet Return Headers 57 0220 12 12 12 12 12 12 12 21 Inlet Outlet Header Cast Iron 01 0008S 1 1 1 1 1...

Страница 30: ...0211 1 1 1 1 1 1 1 30 Ignition Module S8610M 16 0054 1 1 1 1 1 1 1 31 Transformer 40 VA 15 0002 1 1 1 1 1 1 1 NS High Limit EMf 1 SB 14 0118 1 1 1 High Limit EMF 5 SB 14 0009 1 1 1 1 High Limit EMf 1...

Страница 31: ...G 10 0043 2 3 4 5 6 7 8 Orifice 47 LP 10 0038 2 3 4 5 6 7 8 Orifice 49 2 000 3 999 LP 10 0040 2 3 4 5 6 7 8 Orifice 50 4 000 5 999 LP 10 0041 2 3 4 5 6 7 8 Orifice 51 6 000 7 999 LP 10 0042 2 3 4 5 6...

Страница 32: ...side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic the hard wired carbon monoxide detector with alarm and battery back up may be installed on the next adjace...

Страница 33: ...instructions for the installation of the venting system design or the venting system components and 2 A complete parts list for the venting system design or venting system d MANUFACTURER REQUIREMENTS...

Страница 34: ...he tubes and is not covered by the manufacturer s warranty See Installation Instructions for proper pump performance Chemical corrosion no corrosive chemical freon dry cleaning chemicals degreasing li...

Страница 35: ...SPECTRUM INSTALLATION AND OPERATING INSTRUCTIONS Page 35...

Страница 36: ...260 North Elm Street 7555 Tranmere Drive Westfield MA 01085 Mississauga Ontario L5S 1L4 Phone 413 568 9571 Phone 905 670 5888 Fax 413 568 9613 Fax 905 670 5782...