
LOG ENTRY
HeatNet Control V3
Page 84
Log Entry
To access the Log Files, press and hold, the
“Back”
button
for 5 seconds, the control will beep once. There are three
menu options,
SETUP, ADVANCED SETUP,
and
VIEW
LOG
. Place the curser in front of the
VIEW LOG
menu
item and press “Select”.
The Futera III/Fusion-Series H-Net control contains a log
that records the major activity (events) in the operation of
the boiler. This activity includes interlock faults, boiler
starting and stopping events, power cycles, misc. faults, and
types of calls-for-heat (control inputs). Setting the time
clock to an accurate time and date is very useful when
events are recorded, since the control will time stamp each
snapshot. If the system is configured to run with HeatNet,
then only the Master boilers SYSTEM TIME needs to be
entered. The Master will then set the time on all Member
boilers.
The log is primarily used as a troubleshooting and
diagnostic tool, but may be used as a performance tool to
view run time cycles.
An event in time of the boiler’s state is presented via
multiple screens. Each screen event can be stepped through
using the arrow keys.
The top line displays the time and date the event occurred.
In the top right corner, the event # is displayed so that easy
indexing can be done using the arrow keys. The second line
displays the Water temperature of the boiler’s output
(supply) and the Setpoint temperature. The third line
displays the
O
utside
A
ir temperature, and the Modulation.
The bottom line is used to record the control state of the
boiler.
The control state is defined as the Boiler(s) that is running,
the Circulator Pump state, and the ignition condition (Main
Valve, Pilot Valve, Blower, and the Ignition alarm). The #
of boilers that are displayed is limited to 7 if the boiler is the
MASTER. If boilers #8 and up need to be viewed, the
Boiler Control Pro
software will need to be used. The Last
2 characters on the fourth line indicate the heating mode the
control is in. The modes are:
NC = No Call for Heat
HD = Heat Demand (MASTER and Local modulation
control using PID control, MASTER and
MEMBER)
RM = Remote Modulation from 4-20mA input
HF = High Fire from ALL T-inputs closed or the AA
input
1T =
Low Fire from any 1 T-input closed (Low Fire or
High Fire)
2T =
Mid Fire from any 2 T-inputs closed (Low fire or
High Fire )
OP = Option input Active
HT = H-Net Control using the Heat-Link
communications cable
The bottom line is also used to indicate an interlock or limit
that has tripped. It may also indicate a sensor that has failed.
When this occurs, the normal bottom line in the display is
not visible, and the sensor fault is displayed.
For details on messages that appear on the fourth line: See
Appendix B
.
The log may also be viewed using HeatNet Pro or HeatNet
Online.
Figure 62
Log entry display
T
im
e
S
ta
m
p
E
v
e
n
t
n
u
m
b
e
r
Water Setpoint
Modulation PWM %
M = Main Valve open
P = Pilot Valve open
B = Blower ON
P = Circulator Pump
Boiler 1 On
Boiler 2 On
Boiler 3 On
Outside Air
Temperature
NC = No Call for Heat
HD = Heat Demand
RM = Remote Mod 4-20ma
HF,1T, 2T, 3T = T-inputs Fire Rates
HT = H-NET Control
H= Honeywell Alarm
Boiler 7
S = System Pump
D = DHW Pump
(Ver 2.x control)
SET
: 0 5 : 4 2 P
H2O 1 2 7 ° F
MOD%
1
3
1 0 / 1 4
1 3
OA
6 5 ° F
1 4 0 ° F
5 7
P
- - - - - -
H HD
MPB
Содержание FUTERA XLF Series
Страница 21: ...SETUP OPERATION HeatNet Control V3 Page 21 Figure 17 Mixed Boilers Example Condensing Non Condensing...
Страница 27: ...CONTROL METHODS HeatNet Control V3 Page 27 Figure 25 Base loading relay...
Страница 67: ...WIRING CONNECTIONS HeatNet Control V3 Page 67 Figure 49 Jumper Dip Switch Locations...
Страница 73: ...WIRING CONNECTIONS HeatNet Control V3 Page 73 Figure 57 Temperature sensors...
Страница 125: ...WORKSHEET HeatNet Control V3 Page 125 TURNDOWN ALTITUDE CALIBRATION SETTINGS MIN VFD IGN VFD MAX VFD...
Страница 127: ...413 568 9571 Fax 413 568 9613 Page 127...