10 Bushing Test
In this chapter, information regarding bushing power factor/ tan
δ measurement is provided.
According to IEEE C57.152-2013 standard, generally bushings are classified by design as:
•
Condenser type
◦
Insulating liquid-impregnated paper insulation, with interspersed conducting
(condenser) layers or insulating liquid-impregnated paper insulation, continuously
wound with interleaved lined paper layers
◦
Resin-bonded
◦
Resin-impregnated paper insulation, with interspersed conducting (condenser) layers
•
Non-condenser type
◦
Solid core or alternate layers of solid and liquid insulation
◦
Solid mass of homogeneous insulating material (e.g., solid porcelain)
◦
Gas filled
Condenser type bushing includes a series of concentric capacitors from centre conductor to
ground. Some types also include a tap electrode near the ground flange. In the picture below, a
schematic of high voltage bushing can be seen.
90315-1.2 Instruction Manual CAPO
Page 87 of 117