9.5.5 HLT TV
Connect the high voltage from the CAPO to the shorten tertiary voltage terminals of the
transformer.
Connect the measurement Input A to the shorten high voltage terminals of the transformer.
Connect the measurement Input B to the shorten low voltage terminals of the transformer.
If you start the measurement, it will do the following 3 measurements:
GSTg B
C
T
+ C
HT
GSTg A+B
C
T
UST A
C
HT