background image

Catalog No.:  2000.61C 

Effective:  12-01-10 

Replaces:  07-10-09

 

Job: 

 

           

 

Engineer: 

 

           

 

Contractor: 

 

           

 

Prepared By: 

            

 Date:

             

 

Model:  

         

 

 Indoor/Outdoor:  

         

 

 

96% Thermal Efficiency at Full Rate; Up to 99% at Part Load 

100% Factory Fire Tested 

Maximum Outlet Water Temperature: 225°F 

Minimum Inlet Water Temperature: 50°F 

Full Safety Diagnostics with History 

Footprint: Less Than 10.8 ft

2

 

Limited Twenty-Five-Year Thermal Shock Warranty 

Limited Ten-Year Primary Heat Exchanger Warranty 

Limited Ten-Year Secondary Heat Exchanger Warranty 

Full Electronic Modulation, Constant Ratio 4:1 Turndown 

Modulating Controller with LCD Display 

Status Display Lights 

Heat Exchanger 

  Headers 

 Cast Iron – Standard  
 Bronze – Option A-1 

  ASME H Stamped; 160 PSIG MAWP 

  National Board Listed 

  Fin Tubing 

  Copper – Standard 
  Cupro Nickel – Option A-3 

  ASME Powder-Coated Tube Sheet 

  Silicone High Temp O-Rings 

  ASME Pressure Relief Valve 

  60 PSIG – Standard 
             PSIG – Optional 

  150 PSI Air Vent, Auto 

  T&P Gauge, Shipped Loose 

  Stainless Steel Secondary Heat Exchanger 

  Stainless Steel Evaporator Plate 

  Boiler Pump: 120V, 1

, 60Hz; 

 Cast Iron – Standard 
 Bronze – Option 

Control 

  120V, 60Hz, 1Ø, Power Supply 

  120/24V 60Hz Transformer 

  Ignition Module 

  3-Try – Standard 
  Single-Try – Option C-6 

  Hot Surface Ignition (HSI) 

  Remote Flame Sensor 

  Fixed High Limit, Manual Reset, 240°F 

  On/Off Power Switch 

  Flow Switch 

  Blocked Vent Pressure Switch 

  Combustion Air Proving Switch 

  Freeze Protection 

  Alarm Dry Contact 

  Pump Switch 

Control (cont.) 

  Pump Time Delay 

  Diagnostics Panel with LCD Display, 

2 lines, 20 characters 

  Modulating Temperature Control 

  Water Temperature Sensors (3) 

  Cold Water Protection 

  Blocked Condensate Switch 

Burner 

  Ultra-Low NOx: Less than 20 PPM (Natural 

Gas Only) 

Gas Train 

  Fuel 

 Natural Gas 
 Propane 

  Zero Governor Regulator 

  Dual-Seat Combination Valve 

  Electronic Modulating Firing Mode (H7) 

Construction 

  Indoor/Outdoor Construction 

  Enclosed Front Controls 

  PolyTuf Powder Coat Finish 

  Rear Connections (Water, Gas, Vent, 

Electrical, Comb. Air, Cond. Drain) 

  Combustion Air Filter 

  Design Certified ANSI Z21.13/CSA 4.9 

  Front Connection Low Voltage IWiring 

Venting 

  Vent Termination, Cat IV 

  Outdoor or Indoor, Vertical –  

Option D-11 

  Indoor, Horizontal – Option D-15 

  Extractor – Optional, Cat II 

  By others 

 Not required

 

 

Multi-Boiler Digital Temp Controllers 

 B-36  TempTracker Mod+ Hybrid,  

2-4 Boilers, OA Reset 

 B-37  TempTracker Mod+ Hybrid,  

5-10 Boilers, OA Reset 

 B-38   TempTracker Mod+ Hybrid,  

11-16 Boilers, OA Reset 

 B-45  Multi-Mod Platinum,  

2-4 Boilers, OA Reset 

 B-46  Multi-Mod Platinum EMS,  

2-4 Boilers, OA Reset 

 B-47  Multi-Mod Platinum BACNet,  

2-4 Boilers, OA Reset 

 B-48  Multi-Mod Expansion Module, 

1-8 Additional Boilers 

Options 

 D-32  PVC Vent Adapter 

 

(Includes 200ºF Manual High 
Limit) Maximum return water 
temperature allowed 170ºF. 

 F-10 

Low Water Cut-Off, Remote 
Probe 

 I-1 

High Limit, Auto Reset, Adj.,  
100-240°F 

 I-2 

High Limit, Manual Reset, Adj., 
100-240°F 

 S-1 

Low Gas Pressure Switch,  
Manual Reset 

 S-2 

High Gas Pressure Switch, 
Manual Reset 

 Z-12 

Condensate Neutralizer Kit 

Regulatory Agency Requirements 

            

 

 

 

 

 

XTherm

 

- Type H 

    Heating Boilers 

Models 1005-2005 

 

 

 

 

Proudly Made in the USA 