RAYN Installation Guide
Lamp Head and LED Driver
Specifications
Note:
Cables must be installed so that they are visible over the entire
length. Concealing of the cables within walls, floors, ceilings or above
suspended or dropped ceilings is not allowed. Cables must be installed so
they are not subject to strain or damage.
Note:
When utilizing a third-party 1-10 V controller, order a bare-end
control cable (see the complete Lyda System Installation and User Manual for
accessory ordering details).
Environment
Product
Ambient
Temperature
Relative
Humidity
Protection
Lyda lamp head
-10°C to 35°C (14°F to 95°F)
storage maximum
is 45°C (113°F)
20-100%,
condensing,
non-corrosive,
sulfur residue free
suitable
for damp
locations
LED driver
-40°C to 55°C
(-40°F to 131°F)
storage maximum
is 85°C (185°F)
10-100%,
condensing,
non-corrosive
suitable
for damp
locations
Clearance
•
Lamp heads can be ganged together lengthwise, but do not install the Lyda lamp
head against walls or ceilings. Ensure a minimum clearance of 50 mm (2 in)
between the lamp head and other objects such as other lights, the ceiling, or wall
surface for proper cooling.
•
Suspend the lamp head in free-air to allow for proper convection cooling.
Lamp Head and LED Driver
Page 2 of 8
RAYN