Instruction Manual
X 4
X 1
X 1
RTU
Pulse SO
Safety related notification, symbols and instructions that appear in this
operating manual or on the equipment must be strictly followed to
ensure the safety of personnel as well as the instrument. If the
equipment is not used in a manner specified by the manufacturer it may
impair the protection provided by the equipment
•
Do not use the equipment if there are mechanical damage
•
Do not exceed the stated maximum ratings of the device
•
No repairs, maintenance or adjustments are possible
•
Read the complete instruction manual prior to installation or
operating the unit
•
The equipment in its installed state must not come into close
proximity to any heating sources, oils, steam, caustic vapours or
other unwanted process by
-
products
•
Do not use in hazardous or classified location where explosion or
other dangers can be triggered by the device
PRODUCT SAFETY
INSTALLATION PRECAUTIONS
Risk of electric shock!
Only to be installed by a competent person
•
To prevent the risk of electrocution, always isolate and lock
-
off the
power supply to the equipment prior to undertaking any work
•
Always confirm absence of electricity prior to starting work using
appropriate voltage detection equipment
•
Wiring shall be done strictly according to the terminal layout
•
Confirm that all connections are correct before energizing the
equipment
•
Routing of cables shall be way from any internal EMI source
•
Copper cable should be used
•
All wiring to be in accordance with applicable local standards
Specifications
Accuracy
Wiring Input
3Ø 4 wire, 3Ø 3 wire, 2Ø 3 wire, 1Ø 2 wire
Voltage V L
-
N and V L
-
L
±0.5% of full scale
Rated Input Voltage
3x 11...300V AC (L
-
N), 19...519V AC (L
-
L)
Current
±0.5% of full scale
Frequency Range
45...65Hz
Frequency for L
-
N >20V, L
-
L >35V
±0.1% of full scale
CT Primary
1A/5A...10,000A configurable
Active, Reactive and Apparent Power
1%
CT Secondary
1A or 5A (max rating x1.2)
Power Factor
±0.01 of Unity
VT Primary
100...500kV configurable
Active Energy
Class 1 (IEC/EN 62053
-
21)
VT Secondary
100...500V AC (L
-
L) configurable
Reactive Energy
Class 2 (IEC/EN 62053
-
23)
Auxiliary / Power consumption
85...270V AC 45...65Hz / < 8VA
Display Update Rate
1 sec all parameters
Wh Resolution and Default Pulse Weight
Operating / Storage Temperature
-
10…55
°C /
-
20…75
°C
Wh Resolution and Default Pulse Weight
Example
If CT = 100/5A (CT ratio = 20) & VT = 350/350V (VT Ratio = 1)
Wh resolution = 0.1kWh (20 x 1 = <150) | Pulse O/P default = 0.1kwh/pulse
Humidity
0...85% non
-
condensing
Protection Degree (IEC/EN60529)
IP54 Front only (rubber gasket fitted)
Pulse Output
External 5...27V DC / 100mA max
Pulse Resolution / Duration
0.01...99.99kWh per imp / 0.1...2 sec
Communication
Modbus RTU over RS485
MBus (EN13757)
CT Ratio x VT Ratio
<15
<150
<1500
<15k
<150k
≥150
k
Wh / VArh / VAh
0.01k
0.1k
1k
0.01M
0.1M
1M
INT
0.01k
0.1k
1k
0.01M
0.1M
1M
0.001k
0.01k
0.1k
1k
0.01M
0.1M
MECHANICAL INSTALLATION
Installation & Environmental
Panel mounted, indoor used only.
Installation category:
III
Altitude: up to 2000 m
Protection Class:
II
Pollution degree:
II
All terminal covers must be fitted after wiring
EO&E: Document subject to change