Instruction Manual

 

 

                                             

X 4    

 

                                             

X 1

 

                     X 1  

 

RTU

 

Pulse SO

 

Safety related notification, symbols and instructions that appear in this 

operating manual or on the equipment must be strictly followed to 

ensure the safety of personnel as well as the instrument. If the      

equipment is not used in a manner specified by the manufacturer it may 

impair the protection provided by the equipment

 

• 

Do not use the equipment if there are mechanical damage

 

• 

Do not exceed the stated maximum ratings of the device

 

• 

No repairs, maintenance or adjustments are possible

 

• 

Read the complete instruction manual prior to installation or       

operating the unit

 

• 

The equipment in its installed state must not come into close      

proximity to any heating sources, oils, steam, caustic vapours or  

other unwanted process by

-

products

 

• 

Do not use in hazardous or classified location where explosion or 

other dangers can be triggered by the device

 

PRODUCT SAFETY

 

INSTALLATION PRECAUTIONS

 

Risk of electric shock!

 

Only to be installed by a competent person

 

 

• 

To prevent the risk of electrocution, always isolate and lock

-

off the 

power supply to the equipment prior to undertaking any work

 

• 

Always confirm absence of electricity prior to starting work using           

appropriate voltage detection equipment

 

• 

Wiring shall be done strictly according to the terminal layout

 

• 

Confirm that all connections are correct before energizing the   

equipment

 

• 

Routing of cables shall be way from any internal EMI source

 

• 

Copper cable should be used

 

• 

All wiring to be in accordance with applicable local standards

 

Specifications

 

Accuracy

 

Wiring Input

 

3Ø 4 wire, 3Ø 3 wire, 2Ø 3 wire, 1Ø 2 wire

 

Voltage V L

-

N and V L

-

L

 

±0.5% of full scale

 

Rated Input Voltage

 

3x 11...300V AC (L

-

N), 19...519V AC (L

-

L)

 

Current

 

±0.5% of full scale

 

Frequency Range

 

45...65Hz

 

Frequency for L

-

N >20V, L

-

L >35V

 

±0.1% of full scale

 

CT Primary

 

1A/5A...10,000A configurable

 

Active, Reactive and Apparent Power

 

1%

 

CT Secondary

 

1A or 5A (max rating x1.2)

 

Power Factor

 

±0.01 of Unity

 

VT Primary

 

100...500kV configurable

 

Active Energy

 

Class 1 (IEC/EN 62053

-

21)

 

VT Secondary

 

100...500V AC (L

-

L) configurable

 

Reactive Energy

 

Class 2 (IEC/EN 62053

-

23)

 

Auxiliary / Power consumption

 

85...270V AC   45...65Hz  /  < 8VA

 

 

 

Display Update Rate

 

1 sec all parameters

 

Wh Resolution and Default Pulse Weight 

 

Operating / Storage Temperature

 

-

10…55

°C   /   

-

20…75

°C

 

Wh Resolution and Default Pulse Weight  

 

 
 
 
 
 

Example

 

If CT = 100/5A (CT ratio = 20) & VT = 350/350V (VT Ratio = 1)

 

Wh resolution = 0.1kWh (20 x 1 = <150) | Pulse O/P default = 0.1kwh/pulse

 

Humidity

 

0...85% non

-

condensing

 

Protection Degree (IEC/EN60529)

 

IP54 Front only (rubber gasket fitted)

 

Pulse Output

 

External 5...27V DC / 100mA max

 

Pulse Resolution / Duration

 

0.01...99.99kWh per imp / 0.1...2 sec

 

Communication

 

Modbus RTU over RS485

 

MBus (EN13757)

 

CT Ratio x VT Ratio

 

<15

 

<150

 

<1500

 

<15k

 

<150k

 

≥150

k

 

Wh / VArh / VAh

 

0.01k

 

0.1k

 

1k

 

0.01M

 

0.1M

 

1M

 

INT

 

0.01k

 

0.1k

 

1k

 

0.01M

 

0.1M

 

1M

 

 

0.001k

 

0.01k

 

0.1k

 

1k

 

0.01M

 

0.1M

 

MECHANICAL INSTALLATION

 

Installation & Environmental

 

Panel mounted, indoor used only.

 

Installation category: 

III

 

Altitude: up to 2000 m

 

Protection Class: 

II

 

Pollution degree: 

II

 

 

All terminal covers must be fitted after wiring

 

EO&E: Document subject to change

 

x4

 

Содержание RI-F220

Страница 1: ...ernal EMI source Copper cable should be used All wiring to be in accordance with applicable local standards Specifications Accuracy Wiring Input 3Ø 4 wire 3Ø 3 wire 2Ø 3 wire 1Ø 2 wire Voltage V L N and V L L 0 5 of full scale Rated Input Voltage 3x 11 300V AC L N 19 519V AC L L Current 0 5 of full scale Frequency Range 45 65Hz Frequency for L N 20V L L 35V 0 1 of full scale CT Primary 1A 5A 10 00...

Страница 2: ...A For Volt free PLC or digital input voltage must be provided by the addition of a DC PSU Single Core 0 5 4mm2 Ø 2 5mm max Stranded 0 5 2 5mm2 7mm Ø 2 5 mm 0 6 Nm Max 3P4W 3 CTs 1P2W 1 CT 2P3W 2 CTs 2 VTs 2P3W 2 CTs 3P3W 2 CTs 2 VTs 3P3W 2 CTs 3P4W 3 CTs 3 VTs Voltage and current must be from same phase L1 L2 or L3 RS485 PULSE O P RS485 PULSE O P RS485 PULSE O P RS485 PULSE O P RS485 PULSE O P RS4...

Страница 3: ...Primary ID 1 1 1 255 1 250 14 14 Baud rate Modbus MBus 9600 2400 300 19200 bps 1200 9600 15 15 Parity Modbus MBus None Even None Odd Even Even 16 16 Stop Bit Modbus MBus 1 1 1 2 1 17 17 Back Light Off 0000 Never 0000 0 7200 Sec X 18 MBus Secondary ID Serial 0000 0000 9999 9999 18 19 Factory Default No No Yes Does not reset energy demand values 19 20 Reset Energy Demand No No Yes Password 1 Once en...

Страница 4: ...tive Energy kWh L N parameters not displayed For 3P3W Parameters in BOLD not displayed for 1P2W Net Active Energy kWh IM EP L1 IM Reactive Energy kVArh L2 IM Reactive Energy kVArh L3 IM Reactive Energy kVArh L1 EP Reactive Energy kVArh L2 EP Reactive Energy kVArh L3 EP Reactive Energy kVArh Net IM Reactive Energy kVArh Net EP Reactive Energy kVArh Net Reactive Energy kVArh IM EP L1 Apparent Energy...

Отзывы: