Safety related no fica on, symbols and instruc ons that appear in this 

opera ng manual or on the equipment must be strictly followed to 

ensure the safety of personnel as well as the instrument. If the      

equipment is not used in a manner specified by the manufacturer it may 

impair the protec on provided by the equipment

 

· 

Do not use the equipment if there are mechanical damage

 

· 

Do not exceed the stated maximum ra ngs of the device

 

· 

No repairs, maintenance or adjustments are possible

 

· 

Read the complete instruc on manual prior to installa on or       

opera ng the unit

 

· 

The equipment in its installed state must not come into close      

proximity to any hea ng sources, oils, steam, caus c vapours or  

other unwanted process by

-

products

 

· 

Do not use in hazardous or classified loca on where explosion or 

other dangers can be triggered by the device

 

PRODUCT SAFETY

 

INSTALLATION PRECAUTIONS

 

Risk of electric shock!

 

Only to be installed by a competent person

 

 

· 

To prevent the risk of electrocu on, always isolate and lock

-

off the 

power supply to the equipment prior to undertaking any work

 

· 

Always confirm absence of electricity prior to star ng work using           

appropriate voltage detec on equipment

 

· 

Wiring shall be done strictly according to the terminal layout

 

· 

Confirm that all connec ons are correct before energizing the   

equipment

 

· 

Rou ng of cables shall be way from any internal EMI source

 

· 

Copper cable should be used

 

· 

All wiring to be in accordance with applicable local standards

 

Specifica ons

 

Accuracy

 

Wiring Input

 

3Ø 4 wire

 

1Ø 2 wire 

-

 P1, P2, P3

 

Voltage V L

-

N and V L

-

L

 

±0.5% of full scale

 

Rated Input Voltage

 

3x 60...300V AC (L

-

N), 104..520V AC (L

-

L)

 

Current

 

±0.5% of full scale

 

Frequency

 

45...65Hz

 

Frequency for L

-

N > 20V, L

-

L > 35V

 

±0.1% of full scale

 

CT Primary

 

5...10,000A configurable

 

Ac ve, Reac ve and Apparent Power

 

1%

 

CT Secondary

 

0.01...1(1.2)A (Meter Input: 330mV)

 

Power Factor

 

±0.01 of Unity

 

VT Primary

 

100V...10kV AC (L

-

L) configurable

 

Ac ve Energy

 

Class 1 (IEC/EN62053

-

21)

 

VT Secondary

 

100...500V AC (L

-

L) configurable

 

Reac ve Energy

 

Class 2 (IEC/EN62053

-

23)

 

Auxiliary / Voltage Rated Burden

 

Supplied from V1 only / < 8VA

 

 

 

Display Update Rate

 

1 sec all parameters

 

Wh Resolu on and Default Pulse Weight

 

Opera ng / Storage Temperature

 

-

10…55°C   /   

-

20…75°C

 

 

 

 

 

 

 

Example

 

If CT Primary = 200A (CT ra o = 200/1 = 200) & VT = 350/350V (VT Ra o = 1)

 

Wh resolu on = 1kWh (200 x 1 = <1500) | Pulse O/P default = 1kWh/pulse

 

Humidity

 

0...85% non

-

condensing

 

Protec on Degree (IEC/EN60529)

 

IP54 (front of Housing), IP20 (terminals)

 

Communica on

 

Modbus RTU over RS485

 

MBus (EN13757)

 

CT Ra o x VT Ra o

 

<15

 

<150

 

<1500

 

<15k

 

<150k

 

Wh / VAh / VArh

 

0.01k

 

0.1k

 

1k

 

0.01M

 

0.1M

 

INT

 

0.001k

 

0.01k

 

0.1k

 

1k

 

0.01M

 

DIN rail mounted, this device must be installed within a 
suitable IP rated enclosure. Indoor use only.

 

Installa on category: 

III 

(300V L

-

N)

 

Protec on Class: 

II

 

Pollu on degree: 

II

 

Al tude: up to 2000 m

 

 

All terminal covers must be fi ed a er wiring

 

 

 

MECHANICAL INSTALLATION

 

DISMOUNT

 

EO&E: Document subject to change

 

 

 

 1x 3Ø            

 

 1x 1Ø          

 

RI

-

D440

-

G

-

C

 

RI

-

D440

-

G

-

MB

 

 

RTU

 

Pulse SO

 

Содержание RI-D440

Страница 1: ...m any internal EMI source Copper cable should be used All wiring to be in accordance with applicable local standards Specifica ons Accuracy Wiring Input 3Ø 4 wire 1Ø 2 wire P1 P2 P3 Voltage V L N and V L L 0 5 of full scale Rated Input Voltage 3x 60 300V AC L N 104 520V AC L L Current 0 5 of full scale Frequency 45 65Hz Frequency for L N 20V L L 35V 0 1 of full scale CT Primary 5 10 000A configurabl...

Страница 2: ...to 1P2W P1 Voltage Reference V1 must be same phase as CT Connect V2 V3 to N WIRING Modbus MBus Wiring Topology Daisy Chain Star Network Modbus ü û MBus ü ü A B 1 2 Typical Modbus configura on shown For MBus interface follow Wiring Topology below 500m Max 32 meters No Meters 5 10 20 32 Fuse Ra ng 0 5A 1A 1 5A 2A 0 5 Nm Max Single Core 0 5 4mm2 Ø 2 5mm Max Stranded 0 5 2 5mm2 7mm Ø 2 5mm CT phase rot...

Страница 3: ... interval dura on 15 1 30 min ü 14 14 Demand interval length 1 1 30 min ü 15 15 Pulse Weight 0 10 0 01 9 99 kWh imp ü 16 16 Pulse Dura on 200 50 300 mS ü X 17 MBus Secondary ID Serial 0000 0000 9999 9999 ü 17 18 Factory Default No No Yes Does not reset energy demand values ü 18 19 Reset Energy Demand No No Yes Password 1 Once entered reset each value individually ü CONFIGURATION CT Phase Rota on R...

Страница 4: ... Hz x1 Avg Voltage V L N Reac ve Energy kVArh Phase Voltage V L L Avg Voltage V L L Total Current A Frequency Hz Avg Power Factor Phase Ac ve Power kW x2 Phase Reac ve Power kVAr x3 Phase Apparent Power kVA x4 tOt Ac ve Power kW x5 tOt Reac ve Power kVAr x6 tOt Apparrent Power kVA x7 tOt Ac ve Max MD kW x8 tOt Reac ve Max MD kVAr Energy Parameters in BOLD not displayed for 1P2W Voltage Phase Rota ...

Отзывы: