• Lay the heating cable in loops so that
both connection leads can be con-
nected in the same junction box.
• Keep to the given laying spacing.
• The standard laying spacing ranges
from 165 to 275 mm, according to the
specifi c power requirement. A minimum
laying spacing of 55 mm must be main-
tained. Take care that heating cables
do not touch one another, overlap or
cross over.
• The smallest bending radius is 35 mm
(or 5.5 x the heating cable diameter).
(The minimum laying temperature is
–5°C).
• A distance of not less than 50 mm must
be observed between two connection
leads. Crossovers with the rigid con-
nection lead and the MI heating cable
should be covered over with asphalt.
•
Check that the MI heating cable
is completely covered with asphalt.
The fl exible connection lead and the
crossover with the fl exible and the rigid
connection lead must not be covered
with asphalt (see drawing on page 6).
• If the two connection leads are not
going to be routed to a junction box
straight away, they must be protected
from moisture penetration and mechan-
ical damage.
Using Spacers to Fasten the Heating Cable to the Substratum
Laying spacing as given
The tongues are
laid backwards
over the heating
cable, to fi x the
heating cable in
place.
Tongues bent backwards
over the heating cable.
Spacer (prestamped
metal strip)
Heating cable
(heat strip)
Tongue
Spacer (prestamped
metal strip)
Tyco 041654 EM-MI.indd 13
Tyco 041654 EM-MI.indd 13
09/09/04 14:35:43
09/09/04 14:35:43
Содержание EM-MI
Страница 111: ...111 Tyco 041654 EM MI indd 111 Tyco 041654 EM MI indd 111 09 09 04 14 36 00 09 09 04 14 36 00 ...
Страница 112: ...112 Tyco 041654 EM MI indd 112 Tyco 041654 EM MI indd 112 09 09 04 14 36 00 09 09 04 14 36 00 ...
Страница 113: ...113 Tyco 041654 EM MI indd 113 Tyco 041654 EM MI indd 113 09 09 04 14 36 00 09 09 04 14 36 00 ...