6
P/N 016-0171-509 Rev. E
57
INJECTION DIAGNOSTICS AND TROUBLESHOOTING
TABLE 1. LED Status Indicators
ALARMS
TABLE 2. Sidekick Pro ISO Error Codes
LED
Status Display
Logic Power
If logic power is present at the motor control node, the logic power
indicator will be on.
High Current Power
If high current power is present at the motor control node, the high current
power indicator will be on.
CAN Status
The CAN status indicator will flash once per second if the motor control
node is communicating on the CANbus. If the motor control node cannot
communicate via the CANbus, the CAN status indicator will flash four times
per second.
Flow Switch State
The flow switch indicator will flash once per revolution of the injection pump
shaft.
Calibration Switch State The calibration switch indicator will flash when a metal object is passed by
the calibration switch sensor.
Error Description
Possible Cause
Solution
Off Rate Alarm
• Difference
between actual
and target
application rates
has been greater
than 28% for more
than 5 seconds
• Required flow rate is out of range for the injection
pump. Calculate the volume per minute required for
the application and verify rate is within range of the
injection pump.
Low Tank Alarm
• Chemical supply
tank is below the
refill threshold
level
• Refill injection chemical supply tank and reset tank
level in UT display.
Flow Error Alarm
• Flow obstruction
in inlet cartridges
• Perform a pump calibration test. If the pump does not
calibrate properly, remove the intake cartridges and
perform pump maintenance to clear obstructions.
• Chemical supply
tank is out of
chemical
• Refill chemical supply tank and perform the pump
priming procedure.
Flow Error Alarm
• Flow obstruction
in discharge
cartridges
• Perform a pump calibration test. If the pump does not
calibrate properly, remove the discharge cartridges
and perform pump maintenance to clear obstructions.
Low Pressure Alarm
• Injection pressure
is lower than
carrier pressure
• Perform a pump calibration test. If the pump does not
calibrate properly, clean the injection pump inlet and
discharge valves.
• Calibrate the pump transducer.
• Check lines between injection pump and in-line mixer.
• Verify all hand valves are in the correct position.
• Replace the pump transducer.
Содержание Sidekick Pro ISO
Страница 1: ...Sidekick Pro ISO Installation Operation Manual P N 016 0171 509 Rev E 07 17 E29803 Copyright 2017 ...
Страница 8: ...CHAPTER 1 4 Sidekick Pro ISO Installation Operation Manual ...
Страница 16: ...CHAPTER 2 12 Sidekick Pro ISO Installation Operation Manual ...
Страница 46: ...CHAPTER 4 42 Sidekick Pro ISO Installation Operation Manual ...
Страница 70: ...CHAPTER 7 66 Sidekick Pro ISO Installation Operation Manual ...
Страница 80: ...Index 76 Sidekick Pro ISO Installation Operation Manual ...