Manual No. 016-3001-015 Rev. C
51
Initial Set Up and Navigation
Valve Cal 2 (Optional)
The valve cal 2 value may be used to fine tune control valve response and reduce application rate oscillations
when using a Fast Close, PWM or PWM Close control valve.
Fast Close Valves.
When using a fast close valve to control product application, valve cal 2 is utilized to
enable a high resolution rate control for lower application rates. Enter a non-zero value for the time, in
milliseconds, which the valve will be fully opened before switching into high resolution control. For example,
a value of 200 will give the valve a 200 millisecond “burst” at a full 12V to open the control valve from the
closed position before resuming product rate control. A zero value will disable this feature.
Note:
When used with a Fast Close valve, the valve cal 2 feature requires product node software version
1.40 or higher for operation.
PWM or PWM Close Valves.
The valve cal 2 feature is not used with all systems or application equipment.
Refer to the OEM operation manual for instructions on using the valve cal 2 feature with PWM or PWM
Close control valves.
Dual Loop Control Cals
The following calibration values will replace the valve cal and valve cal 2 values if the dual loop control feature
is enabled. See the
section on page 151 for details on the dual loop control mode. Refer to
the
Node Feature Settings Screen (Page 2)
section on page 146 for information on enabling the dual loop
control feature.
Flow Cal
Note:
It is recommended to set the Sgain value prior to making any adjustments to the flow cal value.
The flow cal value has two components which may be used to adjust the response of the application system.
Flow System Gain.
The first digit(s) of the flow cal correspond to a flow system gain between 1 and 99. The
higher the flow system gain, the more aggressive the system will respond to changes in flow rate.
Note:
When entering a flow gain value from 1 to 9, it is not necessary to enter a zero in front of the value.
If the system adjusts to rate control changes too slowly, increase the flow gain digit(s) to increase the
system response rate. If the system overshoots or oscillates around the desired flow rate, decrease the flow
gain digit(s) to help stabilize the system.
Dead Band Digit.
The last, or right most, digit in the flow cal value is the dead band digit. The dead band digit
is the allowable difference between the target rate and the actual application rate. The values range from 1
to 9, where 1 equals 1% difference and 9 equals 9% of the difference.
Flow System Gain
Dead Band
Percentage
103
Содержание OmniSeed Viper Pro
Страница 1: ...Viper Pro Software Version 3 10 OmniSeed Calibration Operation Manual ...
Страница 10: ...Table of Contents viii OmniSeed Viper Pro Calibration Operation Manual ...
Страница 98: ...Chapter 4 86 OmniSeed Viper Pro Installation Operation Manual ...
Страница 150: ...Chapter 6 138 OmniSeed Viper Pro Installation Operation Manual ...
Страница 222: ...Chapter 10 210 OmniSeed Viper Pro Installation Operation Manual ...
Страница 240: ...Chapter 11 228 OmniSeed Viper Pro Installation Operation Manual ...
Страница 250: ...Appendix A 238 OmniSeed Viper Pro Installation Operation Manual FIGURE 1 OmniSeed System Diagram 3 Bin D N 054 5010 003 ...
Страница 251: ...Manual No 016 3001 015 Rev C 239 FIGURE 2 OmniSeed System Diagram 3 Bin D N 054 3001 026 ...
Страница 255: ...Manual No 016 3001 015 Rev C 243 FIGURE 6 Seed Blockage Sensor Cabling More than 60 Sensors D N 054 5002 002 ...
Страница 256: ...Appendix A 244 OmniSeed Viper Pro Installation Operation Manual ...
Страница 284: ...Appendix D 272 OmniSeed Viper Pro Installation Operation Manual ...
Страница 292: ...Appendix G 280 OmniSeed Viper Pro Installation Operation Manual ...
Страница 300: ...Appendix H 288 OmniSeed Viper Pro Installation Operation Manual ...
Страница 304: ...Index 292 OmniSeed Viper Pro Calibration Operation Manual ...
Страница 307: ......