INSTALLATION AND MAINTENANCE INSTRUCTIONS
RE-717MC CONTROL MODULE
SPECIFICATION
Operating Voltage
:
24 VDC Nominal.
Current Draw
:
2 mA Max.(Latched)
Standby Current
:
0.5 mA, 47K EOL.
Line Loss
:
4 VDC Max.
External Supply Voltage
:
Regulated 24V.
Max. Output Current Drive
:
1 Amps.(Supervised)
o
o
.
Temperature Range
:
0 C to 49 C
Humidity
:
10% to 93% Non - condensing.
Dimensions
:
95 mm x 75 mm x 24mm (L x B x H)
Before Installation:
This instruction manual is about quick reference installation guide. For
detailed system information refer the control panel installation manual.
Inform to the operator and authority person that system will be temporarily
out of service, while the module is installed in the existing system.
Note:
Disconnect the power to the control panel before installing the module.
General Instruction:
This control module is intended for the use in intelligent two wire system.
The individual address of the each module is selected by using the DIP
Switch. This module is used to switch the given external power supply to
the notification appliances. The external power supply may be regulated
DC Supply.
Compatibility Requirement:
This control module should be connected to listed compatible control panel
only.
NOTE:
All wiring should be conform to applicable local codes, ordinances, and
regulations.
1. Install module wiring in accordance with the job drawings and
appropriate wiring diagrams.
2. Set the address on the module per job drawings.
Wire should be stripped to the appropriate length. Exposed conductor
should be secured under the clamping plate and should not protrude
beyond the terminal block area.
Caution:
Do not loop wire under terminals & utilize splice connection.
Wiring Configuration for Notification Appliance Circuits (Class B, Style Y)
24 VDC Power Supply
Regulated, Isolated,
Power Limited as per
NFPA 70.
Fire Listed
47K EOL
Resistor
RE-47K
N
A
C
N
A
C
N
A
C
N
A
C
+
+
-
-
To Next
Module
From Panel or
Previous Device
SIGNAL LINE
CIRCUIT (SLC)
28 VDC MAX.
+
-
To Next
Device
+
-
Doc.: No.:RE /IIM/ACM V 1.0
Use only Listed
Compatible Panel
D
* D = NO CONNECTION
* ALL WIRING SHOWN IS SUPERVISED AND POWER LIMITED
NOTE:
RAVEL ELECTRONICS PVT LTD.,
150A, ELECTRONICS INDUSTRIAL ESTATE, PERUNGUDI, CHENNAI - 96 .INDIA.
Ph.: +91-44-2496 1004 / 0825. Fax: +91-44-4204 9599.
E-Mail: [email protected]; www.ravelfire.com