• Display all zone troubles as they occur
• Display all system troubles as they occur
Note:
1.
If any one zone is in walktest, then other zones will operate
normal condition.
2.
The actual alarm zone cannot be selected for walktest
mode.
3.
By Reset the panel using the reset key then walktest
selected zone goes to fire mode.
6.4
System Power:
Power Current
Max.
AH
Capacity
Derating
Factor
Max.
standby
current
Max.
Alarm
current
Max.
standby
time
Max.
alarm
duration
Priomary
(power
supply)
2.5A N/A
N/A 0.04A 0.4A N/A N/A
Secondary
(back up)
2.3A
12Ah
10%
0.4A
2.3A
24 Hrs.
5 Min.
Содержание RE-2504