1.5 Routine Testing
In order to ensure that the system is fully operational, and to comply
with the requirements of UL864 Standard & NFPA – 72, the following
routine attention is recommended:
Daily -
Check the panel to ascertain that it indicates normal operation.
If any fault is indicated check that it has been recorded and the
appropriate actions have been taken e.g. informing to the maintaining
company.
Weekly -
Test at least one detector or call point to confirm the
operation of the panel and the audible alarms. Test a different zone
each week and, if possible, a different device. Keep a record of the
device and zone tested each week. Record and report any
malfunction.
Quarterly -
The responsible person should ensure that every three
months the system is checked by a competent person. Check the
standby batteries and the charger voltage Test at least one device in
each zone to check the panel functions. Check the operation of the
audible alarms and any link to a remote manned centre, Central
Station, etc. Carry out a visual inspection of the installation to check for
alterations or obstructions and issue a certificate of testing.
Annually -
The responsible person should ensure that, in addition to the
quarterly checks, each device on the system is tested and that a visual
inspection is made of the cable fittings and equipment.
Note:
The control panel cabinet should be cleaned periodically by
wiping with a soft, damp cloth.
Do not
use any solvents.
Содержание RE-2504
Страница 5: ...RE DD UM 2508 V1 2 01 4 NOTES...
Страница 6: ...RE DD UM 2508 V1 2 01 5...
Страница 15: ...RE DD UM 2508 V1 2 01 14 Figure 1...
Страница 20: ...RE DD UM 2508 V1 2 01 19 Figure 4 2 5 Internal Arrangement 2 6 Figure 5...
Страница 28: ...RE DD UM 2508 V1 2 01 27 RE 2508 Main Circuit Board RE 25XX ZB R1 Figure 12...
Страница 29: ...RE DD UM 2508 V1 2 01 28 Field Wiring Diagram Figure 13...
Страница 30: ...RE DD UM 2508 V1 2 01 29 Mounting OF RE Monitor Figure 14 Figure 15...