Installation of the unit into the Housing
Installations of the unit into the wall
1. Slide the unit into the housing until it is firmly against the
rear of the housing. Care is required to ensure the foam
sealing strips on the housing remain in position.
2. Connect the air conditioner to the power and position
excess cord length beneath the air conditioner base.
3. Engage the chassis fixing brackets into the bottom housing
rail and secure to the base with the screw provided.
4. Remove the front panel from it's carton and plastic bag
and fit as per the Installation lnstruction.
5. Switch unit on. Check for operation of the unit and check
for vibration in the installation.
6. Fit the drain pan to the housing and run a drain line to a
suitable location if required.
Alternative method of installation if external
support cannot be provided.
FLASH OR SEAL AROUND EXTERNAL
WALL FRAME OR ARCHITRAVE
STURDY TIMBER
FRAME
TIMBER FRAMED
WALL OR PARTITION
SOLID TIMBER SUPPORT
STEADYING BRACKET
(ONE PER SIDE)
DRAIN PAN
ENSURE LOUVRES
ARE ENTIRELY
OUTSIDE THE WALL
AIR IN
AIR IN
AIR OUT
100mm minimum
OPTION A
AIR IN
LOUVRE
BRICK
WALL
O
45 BRICK CUT AWAY
TO CLEAR LOUVRES
FRONT
AIR OUT
AIR IN
AIR IN
TOP
VIEW
O
45 BRICK CUT AWAY
TO CLEAR LOUVRES
100mm
BRICK
WALL
100mm
OPTION B
Step 1
Remove the air conditioner from it's packaging, remove fixing
screws and slide the air conditioner out of it's housing (Refer
to Installation Steps).
Step 2
Prepare the hole in the wall so that the bottom of the housing
is well supported, the top has minimum clearance and the air
inlet louvers have clearance as shown below in options A and
B. Holes from the outside through to the cavity should be
sealed. The housing should slope down towards the rear by
about 5mm to allow water formed during operation to drain.
Step 3
Install the housing into the wall and secure. Ensure the foam
seals are not damaged. Flash, seal or fill gaps around the
inside and outside to provide satisfactory appearance and
protection against the weather, insects and rodents.
Installation of the Housing
NOTE: UNIT MAY BE SUPPORTED BY A
SOLID FRAME FROM BELOW OR
BY A HANGER FROM A SOLID
OVERHEAD SUPPORT.
Preferred method of installation into a timber
framed wall, partition or window.
FLASH OR SEAL AROUND EXTERNAL
WALL FRAME OR ARCHITRAVE
STURDY TIMBER
FRAME ALL ROUND
UNIT
TIMBER FRAMED
WALL OR PARTITION
EXTERNAL SUPPORT
FRAME AT BALANCE
POINT OF A/C
ALTERNATIVELY, BRACKETS
AS ILLUSTRATED BELOW
MAY BE USED.
DRAIN PAN
Содержание RC-X7U
Страница 18: ... ...
Страница 19: ...3 ...
Страница 20: ...O 18 43 C T1 O 17 32 C T1 注 ...
Страница 21: ...5 Õ µ ú Á ã þ Ã û Æ 附件 1 1 螺絲 排水接頭 1 排水接盤 2 注 本說明書中的所有插圖僅供說明用途 您的空調可能略有不同 以實際形狀為準 密封圈 用於排水接頭 數量 ...
Страница 22: ...LED屏顯示回風溫度 ...
Страница 23: ...某些型號沒有中風速 自動 模式 風速固定為 高 ...
Страница 24: ...8 只限冷暖型號 注意 如果在本機處於AUTO模式時激活SLEEP模式 風扇馬達將立即變為LOW速度模式 自動 AUTO ...
Страница 27: ...11 ...
Страница 28: ......
Страница 29: ......
Страница 30: ...異常操作 ...