Chapter 8: Using the Command Line Interface
288
Example 1 - Environmental Sensor Naming
The following command assigns the name "Cabinet humidity" to the
environmental sensor with the ID number 4.
config:#
externalsensor 4 name "Cabinet humidity"
Example 2 - Sensor Threshold Selection
The following command sets the environmental sensor #1 to use the
default thresholds, including the deassertion hysteresis and assertion
timeout, as its threshold settings.
config:#
externalsensor 1 useDefaultThresholds true
Sensor Threshold Configuration Commands
A sensor configuration command begins with
sensor
. You can use the
commands to configure the threshold, hysteresis and assertion timeout
values for any sensor associated with the following items:
Inlets
Inlet poles (for three-phase PDUs only)
Overcurrent
protectors
Environmental
sensors
It is permitted to assign a new value to the threshold at any time
regardless of whether the threshold has been enabled.
Commands for Inlet Sensors
A sensor configuration command for inlets begins with
sensor inlet
.
Содержание PXE
Страница 1: ...Copyright 2014 Raritan Inc PXE 0C v3 0 E August 2014 255 80 0008 00 Raritan PXE User Guide Release 3 0...
Страница 12: ...Contents xii To Assert and Assertion Timeout 352 To De assert and Deassertion Hysteresis 354 Index 357...
Страница 16: ......
Страница 50: ...Chapter 5 Using the PDU 34 4 Pull up the operating handle until the colorful rectangle or triangle turns RED...
Страница 200: ...Chapter 6 Using the Web Interface 184 10 To print the currently selected topic click the Print this page icon...
Страница 339: ...Appendix A Specifications 323 RS 485 Pin signal definition al 4 5 6 D bi direction al Data 7 8...
Страница 353: ...Appendix D LDAP Configuration Illustration 337 5 Click OK The PX_Admin role is created 6 Click Close to quit the dialog...
Страница 380: ...Index 364 Z Zero U Products 1...
Страница 381: ......