Appendix F: PX3 Models with Residual Current Monitoring
597
Running RCM Self-Test
You can perform the RCM self-test by operating the front panel buttons.
To disable or enable this front panel function, see
Disabling or Enabling
Front Panel RCM Self-Test
(on page 593). By default, this function is
enabled.
To run RCM self-test:
1.
Press
/
or
/
to access the
Main Menu
(on page 96).
2.
Press
/
or
/
to select "Residual Current," and press
/
.
3.
The LCD display shows the RCM information for the inlet(s).
4.
Press
/
to perform RCM self-test on the selected inlet.
If your PDU has multiple inlets, press
/
or
/
to
select the desired inlet and press
/
.
5.
A confirmation message displays. By default, Yes is selected.
To execute the RCM self-test, press
/
.
To cancel the RCM self-test, do either of the following:
- Press
/
.
- Press
/
or
/
to select No and then press
/
.