![Raritan PX3-1000 series Скачать руководство пользователя страница 614](http://html1.mh-extra.com/html/raritan/px3-1000-series/px3-1000-series_user-manual_3780217614.webp)
Appendix F: PX3 Models with Residual Current Monitoring
592
IEC 62020 specification
PX3 with RCM characteristics
Connection of load
conductors
Monitored line is directly connected.
Fault indicating means
Visual, with other output signals.
Ability to directly
discriminate
Directionally non-discriminating.
Rated residual operating
current
0.5A (highest value).
Residual currents with
direct current components
Model dependent.
Models ending in -M5 are Type A, -M11 are Type B.
RCM Self-Test
PX3 with RCM have a built-in self-test feature that performs these
functions:
When residual current is less than 3mA, 15mA is momentarily added
to determine whether the low reading is due to a faulty sensor. The
residual current added is done in a safe manner which does not run
current into ground or pose operator risk.
The RCM state sensor changes to SELF-TEST and then back to its
original state if self-test passes, or to the FAILURE state if self-test
fails. These state changes are useful to verify your monitoring
systems (SNMP, syslog, or email) are correctly set up to receive PX3
event notifications.
Note: If self-test fails, the FAILURE state persists until another self-test
runs and passes.
Web Interface Operations for RCM
The RCM is a PX3 inlet sensor. To view, configure or run self-test, click
Inlet in the
Menu
(on page 132).
Checking RCM State and Current
A section titled 'Residual Current Monitor' is available on the Inlet page,
showing both the present RCM state and residual current.
To check RCM state and current on the Inlet page:
1.
Click Inlet. See
Web Interface Operations for RCM
(on page 591).
2.
Locate the Residual Current Monitor section on the Inlet page.
Содержание PX3-1000 series
Страница 5: ......
Страница 92: ...Chapter 4 Connecting External Equipment Optional 70...
Страница 668: ...Appendix J RADIUS Configuration Illustration 646 Note If your PX3 uses PAP then select PAP...
Страница 669: ...Appendix J RADIUS Configuration Illustration 647 10 Select Standard to the left of the dialog and then click Add...
Страница 670: ...Appendix J RADIUS Configuration Illustration 648 11 Select Filter Id from the list of attributes and click Add...
Страница 673: ...Appendix J RADIUS Configuration Illustration 651 14 The new attribute is added Click OK...
Страница 674: ...Appendix J RADIUS Configuration Illustration 652 15 Click Next to continue...
Страница 722: ...Appendix L Integration 700 3 Click OK...