Chapter 8: Using the Command Line Interface
465
Outlet Configuration Commands
An outlet configuration command begins with
outlet. Such a command
allows you to configure an individual outlet.
Changing the Outlet Name
This command names an outlet.
config:#
outlet <n> name "<name>"
Variables:
<n> is the number of the outlet that you want to configure.
<name> is a string comprising up to 32 ASCII printable characters.
The <name> variable must be enclosed in quotes when it contains
spaces.
Changing an Outlet's Default State
This section applies to outlet-switching capable models only.
This command determines the initial power condition of an outlet after
the PX3 powers up.
config:#
outlet <n> stateOnDeviceStartup <option>
Variables:
<n> is the number of the outlet that you want to configure.
<option> is one of the options:
off, on, lastKnownState and
pduDefined.
Option
Description
off
Turn off the outlet.
on
Turn on the outlet.
lastKnownState Restore the outlet to the state prior to last PDU
power down.
pduDefined PDU-defined
setting.
Содержание PX3-1000 series
Страница 5: ......
Страница 92: ...Chapter 4 Connecting External Equipment Optional 70...
Страница 668: ...Appendix J RADIUS Configuration Illustration 646 Note If your PX3 uses PAP then select PAP...
Страница 669: ...Appendix J RADIUS Configuration Illustration 647 10 Select Standard to the left of the dialog and then click Add...
Страница 670: ...Appendix J RADIUS Configuration Illustration 648 11 Select Filter Id from the list of attributes and click Add...
Страница 673: ...Appendix J RADIUS Configuration Illustration 651 14 The new attribute is added Click OK...
Страница 674: ...Appendix J RADIUS Configuration Illustration 652 15 Click Next to continue...
Страница 722: ...Appendix L Integration 700 3 Click OK...