503
You can accomplish part or all of the following tasks simultaneously by
plugging a USB flash drive which contains one or several special
configuration files into the PX.
Configuration changes
Firmware upgrade
Downloading diagnostic data
Tip: You can also accomplish the same tasks via the TFTP server in a
DHCP network. See
Bulk Configuration or Firmware Upgrade via
DHCP/TFTP
(on page 514).
To use a USB drive to configure the PX or upgrade firmware:
1. Verify that both the USB drive and your PX meet the requirements.
See
System and USB Requirements
(on page 504).
2. Prepare required configuration files. See
Configuration Files
(on
page 504).
3. Copy required configuration files to the root directory of the USB
drive.
For firmware upgrade, an appropriate firmware binary file is also
required.
4. Plug the USB drive into the USB-A port of the PX.
5. The initial message shown on the front panel display depends on the
first task performed by the PX.
If no firmware upgrade task will be performed, a happy smiley as
shown below is displayed after around 30 seconds.
=-]
If the USB drive contains the firmware upgrade data, the PX first
performs the firmware upgrade, showing the upgrade message
on the front panel display, and then shows the happy smiley
when the firmware upgrade completes successfully. See
Firmware Upgrade via USB
(on page 513).
6. After the happy smiley appears, press and hold one of the control
buttons next to the front panel display for one second until the
display turns blank.
7. Wait for several seconds until the PX resumes normal operation,
indicated by the normal message of the front panel display.
Appendix C Configuration or Firmware Upgrade
with a USB Drive
Содержание PX2-1000 SERIES
Страница 5: ......
Страница 71: ...Chapter 4 Connecting External Equipment Optional 52...
Страница 231: ...Chapter 6 Using the Web Interface 212 8 Click OK...
Страница 570: ...Appendix G LDAP Configuration Illustration 551 5 Click OK The PX_Admin role is created 6 Click Close to quit the dialog...
Страница 589: ...Appendix I RADIUS Configuration Illustration 570 Note If your PX uses PAP then select PAP...
Страница 590: ...Appendix I RADIUS Configuration Illustration 571 10 Select Standard to the left of the dialog and then click Add...
Страница 591: ...Appendix I RADIUS Configuration Illustration 572 11 Select Filter Id from the list of attributes and click Add...
Страница 594: ...Appendix I RADIUS Configuration Illustration 575 14 The new attribute is added Click OK...
Страница 595: ...Appendix I RADIUS Configuration Illustration 576 15 Click Next to continue...
Страница 627: ...Appendix K Integration 608 3 Click OK...
Страница 647: ...Index 629 Z Zero U Connection Ports 74 Zero U Products 2...