Chapter 6: Using the Web Interface
281
Changing Default Thresholds
The default thresholds are the initial threshold values that automatically
apply to numeric environmental sensors. These values are configured on
a sensor type basis, which include:
Temperature sensors
Humidity sensors (both relative and absolute humidity)
Air pressure sensors
Air flow sensors
Vibration sensors
Note that changing the default thresholds re-determine the initial
thresholds applying to the environmental sensors that are added or
detected later on.
In addition, changing the default thresholds also change the thresholds
of those environmental sensors where the default thresholds have been
selected as their threshold option. See
Configuring Environmental
Sensors or Actuators
(on page 278).
To change the default threshold settings:
1. Click Peripheral Devices in the left pane.
2. Click Default Thresholds Setup on the Peripheral Devices page. A
dialog appears, showing a list of all numeric environmental sensor
types.
3. Select the desired sensor type.
4. Click Edit or double-click that sensor type to adjust its threshold
settings, deassertion hysteresis or assertion timeout.
To enable any threshold, select the corresponding checkbox. To
disable a threshold, deselect the checkbox.
After any threshold is enabled, type an appropriate numeric value
in the accompanying text box.
To set the deassertion hysteresis, type a numeric value in the
Deassertion Hysteresis field. See
"To De-assert" and
Deassertion Hysteresis
(on page 597).
To set the assertion timeout, type a numeric value in the
Assertion Timeout (samples) field. See
"To Assert" and
Assertion Timeout
(on page 595).
5. Repeat the above step to modify the threshold settings of other
numeric sensor types.
6. Click
OK.
Содержание PX2-1000 SERIES
Страница 5: ......
Страница 71: ...Chapter 4 Connecting External Equipment Optional 52...
Страница 231: ...Chapter 6 Using the Web Interface 212 8 Click OK...
Страница 570: ...Appendix G LDAP Configuration Illustration 551 5 Click OK The PX_Admin role is created 6 Click Close to quit the dialog...
Страница 589: ...Appendix I RADIUS Configuration Illustration 570 Note If your PX uses PAP then select PAP...
Страница 590: ...Appendix I RADIUS Configuration Illustration 571 10 Select Standard to the left of the dialog and then click Add...
Страница 591: ...Appendix I RADIUS Configuration Illustration 572 11 Select Filter Id from the list of attributes and click Add...
Страница 594: ...Appendix I RADIUS Configuration Illustration 575 14 The new attribute is added Click OK...
Страница 595: ...Appendix I RADIUS Configuration Illustration 576 15 Click Next to continue...
Страница 627: ...Appendix K Integration 608 3 Click OK...
Страница 647: ...Index 629 Z Zero U Connection Ports 74 Zero U Products 2...