Chapter 6: Using the Web Interface
221
Request LHX/SHX Maximum Cooling
If Schroff LHX/SHX Support is enabled, the LHX/SHX-related actions will
be available. See
Enabling and Disabling Schroff LHX/SHX Heat
Exchanger Support
(on page 310).
The "Request LHX/SHX Maximum Cooling" action applies the maximum
cooling to the SHX-30 device only. The LHX-20 and LHX-40 devices do
not support this feature.
In the maximum cooling mode, an SHX-30 device runs at 100% fan
speed and the cold water valve is open 100%.
To request maximum cooling for SHX-30:
1. Choose Device Settings > Event Rules. The Event Rules Settings
dialog opens.
2. Click the Actions tab.
3. Click
New.
4. In the "Action name" field, type a new name for the action. The
default name is New Action <number>, where <number> is a
sequential number starting at 1.
5. In the Action field, click the drop-down arrow and select the desired
action: Request LHX/SHX maximum cooling.
6. Click
OK.
Send a Snapshot via Email
This option notifies one or multiple persons for the selected events by
emailing snapshots or videos captured by a connected Logitech
®
webcam.
To create a send snapshot via email action:
1. Choose Device Settings > Event Rules. The Event Rules Settings
dialog opens.
2. Click the Actions tab.
3. Click
New.
4. In the "Action name" field, type a new name for the action. The
default name is New Action <number>, where <number> is a
sequential number starting at 1.
5. In the Action field, click the drop-down arrow and select the desired
action: Send snapshots via email.
6. In the "Recipients email addresses" field, specify the email
address(es) of the recipient(s). Use a comma to separate multiple
email addresses.
7. To use the SMTP server specified in the SMTP Server Settings
dialog, select the Use Default SMTP Server checkbox.
Содержание PX2-1000 SERIES
Страница 5: ......
Страница 71: ...Chapter 4 Connecting External Equipment Optional 52...
Страница 231: ...Chapter 6 Using the Web Interface 212 8 Click OK...
Страница 570: ...Appendix G LDAP Configuration Illustration 551 5 Click OK The PX_Admin role is created 6 Click Close to quit the dialog...
Страница 589: ...Appendix I RADIUS Configuration Illustration 570 Note If your PX uses PAP then select PAP...
Страница 590: ...Appendix I RADIUS Configuration Illustration 571 10 Select Standard to the left of the dialog and then click Add...
Страница 591: ...Appendix I RADIUS Configuration Illustration 572 11 Select Filter Id from the list of attributes and click Add...
Страница 594: ...Appendix I RADIUS Configuration Illustration 575 14 The new attribute is added Click OK...
Страница 595: ...Appendix I RADIUS Configuration Illustration 576 15 Click Next to continue...
Страница 627: ...Appendix K Integration 608 3 Click OK...
Страница 647: ...Index 629 Z Zero U Connection Ports 74 Zero U Products 2...