Chapter 6: Using the Web Interface
219
3. In the "Action name" field, type a new name for the action. The
default name is New Action <number>, where <number> is a
sequential number starting at 1.
4. In the Action field, click the drop-down arrow and select the desired
action: External beeper.
5. From the Beeper Port drop-down list, select the port where the
external beeper is connected. This port is the FEATURE port.
6. From the Beeper Action drop-down list, select an action for the
external beeper to carry out.
Alarm: Causes the external beeper to sound an alarm cycle
every 20 seconds - stays on for 0.7 seconds and then off for
19.3 seconds.
On: Turns on the external beeper so that it buzzes continuously.
Off: Turns off the external beeper so that it stops buzzing.
7. Click
OK.
Note: If you create an event rule for the external beeper but disconnect it
when an event causes it to beep, the beeper no longer beeps after it is
re-connected even though the event triggering the beeping action
remains asserted.
Log an Event Message
This option records the selected events in the internal log.
To create a log event message:
1. Choose Device Settings > Event Rules. The Event Rules Settings
dialog opens.
2. Click the Actions tab.
3. Click
New.
4. In the "Action name" field, type a new name for the action. The
default name is New Action <number>, where <number> is a
sequential number starting at 1.
5. In the Action field, click the drop-down arrow and select the desired
action: Log event message.
6. Click
OK.
Содержание PX2-1000 SERIES
Страница 5: ......
Страница 71: ...Chapter 4 Connecting External Equipment Optional 52...
Страница 231: ...Chapter 6 Using the Web Interface 212 8 Click OK...
Страница 570: ...Appendix G LDAP Configuration Illustration 551 5 Click OK The PX_Admin role is created 6 Click Close to quit the dialog...
Страница 589: ...Appendix I RADIUS Configuration Illustration 570 Note If your PX uses PAP then select PAP...
Страница 590: ...Appendix I RADIUS Configuration Illustration 571 10 Select Standard to the left of the dialog and then click Add...
Страница 591: ...Appendix I RADIUS Configuration Illustration 572 11 Select Filter Id from the list of attributes and click Add...
Страница 594: ...Appendix I RADIUS Configuration Illustration 575 14 The new attribute is added Click OK...
Страница 595: ...Appendix I RADIUS Configuration Illustration 576 15 Click Next to continue...
Страница 627: ...Appendix K Integration 608 3 Click OK...
Страница 647: ...Index 629 Z Zero U Connection Ports 74 Zero U Products 2...