PURASAN

® 

EX Hold n’ Treat

OPERATION, MAINTENANCE AND INSTALLATION INSTRUCTIONS

(Models PST*EX  [*specify 12,24] Manufactured after December 2013)

 

The PURASAN

®

EX is a U. S. Coast Guard Certified Type I Marine Sanitation Device for use on unin

-

spected vessels 65 feet and under. It must be operated within navigable waters inside the three mile limit 

that are not declared Federal No Discharge Zones (NDZ) by the U.S. Environmental Protection Agency 

(EPA).  Other countries - check with local authorities.

The PURASAN

®

EX is designed for recreational use and accommodates most marine toilets.  The 

PURASAN

®

EX is available in 12 or 24 VDC. 

DESCRIPTION:

Each time the transfer pump cycles an equal amount of previously treated waste is discharged. The pump

-

ing action of the transfer pump moves the waste through the 

PURASAN

®

EX

 and out. 

Water is diverted to the Tablet Dispenser during the treatment cycle, creating a halogen solution during hold 

time. After the hold time, the Drain Manifold and Air Pump turn on and the solution drains into the Treat

-

ment Unit.The first chamber macerates to reduce particle size and uniformly mix the waste with injected 

halogen solution. The second chamber mixes to ensure uniform treatment of its contents. 

              

THE FOLLOWING ARE CAUTIONARY STATEMENTS THAT MUST BE READ AND 

FOLLOWED DURING BOTH INSTALLATION AND OPERATION

  

 

 WARNING:

  Raritan Engineering Company, Inc. recommends that a qualified person or electrician install this product.  

Equipment damage, injury to personnel or death could result from improper installation.  Raritan Engineering 

Company, Inc. accepts no responsibility or liability for damage to equipment, or injury or death to personnel 

that may result from improper installation or operation of this product.

   WARNING:  HAZARD OF SHOCK AND FIRE

   

 

Always use recommended fuse or circuit breaker and wire size.  

 

 

 

 

 

   

WARNING:  HAZARD OF FLOODING - 

When leaving the boat unattended always be sure seacocks are closed.  Any 

installation made below waterline should have double hose clamps securing lines.  

The halogen disinfectant 

is corrosive to aluminum, copper and steel.  The plumbing system must not include any aluminum, 

copper or steel fittings, piping or holding tanks. 

IMPORTANT SAFETY INSTRUCTIONS FOR HANDLING PURASAN

®

 TABLETS AND SOLUTION 

 

 PURASAN

®

 EX disinfecting tablets are a strong oxidizing agent and highly corrosive. Use or contact 

with oil, acids, petroleum products, reducing agents or other chlorine compounds such as swimming 

pool tablets, is extremely dangerous

 

 

Fire or explosion could result. Improper use of this tablet may cause personal injury or property damage. 

Tablets may be fatal if swallowed and tablet dust is irritating to the eyes, nose and throat. Keep out of 

reach of children and do not allow tablets or solution of tablets to contact skin, eyes or clothing. Handle 

and store tablets as per instructions provided with packaging. Contact Raritan if handling instructions 

are missing. Store only in sealed original container in well-ventilated area. Read tablet container label 

carefully prior to use. It is unsafe and violation of Federal law to use tablets in a manner inconsistent 

with its labeling.

 WARNING:

 WARNING:

The Hold n’ Treat is designed to integrate both a Type I and Type III MSD (Marine Sanitation Device) to 

provide the user with a system that will be legal in all areas.  

All waste is stored in a holding tank and the treatment mode will determine how the waste is processed. 

This system eliminates the need for pump-out stations in most areas.

L519 _0919jlc 

Содержание 21SRP1512

Страница 1: ...o personnel that may result from improper installation or operation of this product WARNING HAZARD OF SHOCK AND FIRE Always use recommended fuse or circuit breaker and wire size WARNING HAZARD OF FLOO...

Страница 2: ...lding tank is above the LOW LEVEL treatment cycle starts Macerator pump is activated and moves approximately 1 gallon of waste from the holding tank to the treatment tank Treatment cycles runs for 2 m...

Страница 3: ...level 3 If cycle completes normal there is a 8 second pause before next cycle will start During this pause none of the buttons except No Discharge mode button is functional MAINTENANCE CAUTION Do not...

Страница 4: ...nstructions in the Owner s Manual for that particular toilet Recommissioning IMPORTANT Do not open shut off valve feeding control module until Treatment Tank is full Do not operate PURASAN EX until Tr...

Страница 5: ...er Size with macerator pump Fuse Specifications 3 1 4 8 3 cm 4 3 4 12 cm SWITCH PANEL DIMENSIONS Depth 8 22 3cm Width 16 40 6cm TREATMENT UNIT DIMENSIONS Height 13 34 3cm TABLET DISPENSER DIMENSIONS F...

Страница 6: ...ubing 6 3 8 ID tubing For Treatment unit 6 3 8 ID tubing Switch Panel Switch Panel Gasket Tablet Dispenser Inside the module Drain Manifold Water Valve SPC control box 6 black and orange wire to conne...

Страница 7: ...e wall FIG 6 Switch Panel Cable Supplied is 16 feet 1 Locate in head compartment where indicator lights will be visible 2 Using base plate mark the cutout for the panel See FIG 7 3 Route cable between...

Страница 8: ...FE tape or nonpermanent thread sealing compound on threaded PVC fittings and connections Avoid low areas in hose that would allow untreated waste to collect 1 Connect discharge of macerator to one int...

Страница 9: ...odule Using cable clamp secure cable on the wall near dispenser 2 Connect sensor cable to control module SPC Note Complete programming for Fill and Empty timing before connecting shutoff valve key swi...

Страница 10: ...PTIONAL SensaLevelTM BLACK WHITE OR RED BLACK WATER SOLENOID AIR PUMP DRAIN MAINIFOLD NEG POS 3 AMP FUSE TO POS TERMINAL BLACK 12AWG RED 12AWG BLUE BLACK RED CABLE CABLE RED 86 30 87 85 FUSE 25 AMP 12...

Страница 11: ...you have left program mode Macerator Pump FIG 11 FILL EMPTY ERROR Treatment PROGRAMMING After hold time air pump and drain valve will drain solution Make sure that water is drained from entire tube u...

Страница 12: ...1 22 57 48 47 46 45 44 43 40 41 70 71 80 81 85 84 86 82 83 72 27 39 37 38 36 32 54 53 36 31 30 58 41 137W 221351W 12V 221352W 24V 41 100AW 162000WA SPC 59 66 64 67 68 69 28 29 24 33 34 35 50 55 65 L51...

Страница 13: ...seal 34 41 138 B Plunger 35 41 138A Washer for plunger 36 F204 6 32 x 3 8 Flat head mach screw 4 37 LWS Spring 38 F203 Washer 5 16 x 3 4 39 F233 Spring Roll Pin 50 41 187 Shaft Boot 53 41 152 Base Pla...

Страница 14: ...QUENCE Note Fill time and Empty times are programmable Total treatment time is 120 seconds FILL CYCLE HOLD CYCLE EMPTY CYCLE DRAIN MANIFOLD PORTS Fig13 Water in Fill Air in Air to disp Empty To tank C...

Страница 15: ...tablet dispenser Press empty button to run air pump and clear any clog Clogged Check valve treatment tank adapter Clean or replace check valve 41 170 located on the tank Water fill time not programme...