background image

TFP415

Page 5 of 6

(a) For coverage area dimensions less than or between those indicated, it is necessary to use the minimum required flow for the next

highest coverage area for which hydraulic design criteria are stated.

(b) Width (backwall where sprinkler is located) x Length (horizontal throw of sprinkler).

(c) Requirement is based on minimum flow in GPM (LPM) from each sprinkler. The associated residual pressures are calculated using

the nominal K-factor. Refer to Hydraulic Design Criteria Section for details..

TABLE B

NFPA 13D AND NFPA 13R WET PIPE HYDRAULIC DESIGN CRITERIA

FOR THE SERIES LFII (TY3334)

RESIDENTIAL HORIZONTAL SIDEWALL AND RECESSED HORIZONTAL SIDEWALL SPRINKLERS

FOR SPRINKLERS LOCATED ALONG A SLOPE AND DISCHARGING ACROSS THE SLOPE

(Greater Than 2 Inch Rise for 12 Inch Run Up To 4 Inch Rise for 12 Inch Run)

Maximum
Coverage

Area

(a)

Width x Length

(b)

Ft. x Ft.
(m x m)

Maximum

Spacing

Ft.

(m)

Minimum Flow

(c)

and Residual Pressure

Two sprinkler design with the sprinklers located along the slope and positioned to

discharge across the slope.

.

Top-Of-Deflector- To- Ceiling:

4 to 6 Inches (100 to 150 mm)

155°F/68°C

175°F/79°C

155°F/68°C

175°F/79°C

Top-Of-Deflector- To- Ceiling:

6 to 12 Inches (150 to 300 mm)

16 x 16

(4,9 x 4,9)

16

(4,9)

24 GPM (90,8 LPM)

18.4 psi (1,27 bar)

24 GPM (90,8 LPM)

18.4 psi (1,27 bar)

24 GPM (90,8 LPM)

18.4 psi (1,27 bar)

24 GPM (90,8 LPM)

18.4 psi (1,27 bar)

ELEVATION

12"

MAXIMUM

4"