SECTION 14: T
ROUBLESHOOTING
45 of 59
14.4 Troubleshooting for Gas Valves
14.5 Troubleshooting for Flue Blower
Valve faulty.
Replace with one of
correct type.
Fault elsewhere.
Correct pressure problem.
If problems persist, contact
Rapid Engineering LLC at
www.rapidengineering.com
Valve Operating
TROUBLESHOOT ENDS.
No
Yes
Valve or ignition control
faulty. Replace with
one of correct type.
Does gas pressure at
outlet of valve return to zero or
lower when valve turns off?
No
Yes
Does gas pressure at outlet
of the valve rise when
valve turns on?
No
Yes
Is gas pressure at inlet of the
valve correct for gas type?
Note pressure found.
No
Yes
START
If problems persist, contact
Rapid Engineering LLC at
www.rapidengineering.com
Blower Operating
TROUBLESHOOT ENDS.
No
Blower motor faulty.
Replace with correct type.
Check blower motor leads
for loose connections.
Correct power
supply problem.
Yes
START
Does
blower
turn on and
off while burner is firing
continously?
No
Yes
Does flue blower run
automatically when there
is a call for heat?
No
Yes
For your safety and optimum heater performance, use only genuine replacement parts sold and supplied
by Rapid Engineering LLC.
Conduct start-up procedure as shown on Page 29, Section 11.
Содержание UHAT 150
Страница 2: ......
Страница 4: ......
Страница 8: ......
Страница 50: ...UHA STANDARD UNIT HEATER INSTALLATION OPERATION AND SERVICE MANUAL 42 of 59 14 1 General...
Страница 65: ...SECTION 16 SPECIFICATIONS 57 of 59 16 4 Dimension Data for Models UHA T M X S 300 400...
Страница 68: ......
Страница 69: ......
Страница 70: ......
Страница 71: ......
Страница 72: ......