Table 5: SunSpec model 307, base meteorological
Field
Type
Address
Offset
Block
Offset
Size
Name
Label
Value
Type
Unit
SF
R/W
Description
Notes
Header
0
1
ID
Base Met
307
uint16
R
Base Meteorological Model
This model
supersedes
model 301
Header
1
1
L
11
uint16
R
Model Length
Fixed
Block
2
0
1
TmpAmb
Ambient
Temperature
int16
C
-1
R
Fixed
Block
3
1
1
RH
Relative
Humidity
int16
Pct
R
Fixed
Block
4
2
1
Pres
Barometric
Pressure
int16
HPa
R
Fixed
Block
5
3
1
WndSpd
Wind Speed
int16
m/s
R
Fixed
Block
6
4
1
WndDir
Wind
Direction
int16
deg
R
Fixed
Block
7
5
1
Rain
Rainfall
int16
mm
R
Fixed
Block
8
6
1
Snw
Snow Depth
int16
mm
R
Fixed
Block
9
7
1
PPT
Precipitation
Type
int16
R
Precipitation Type (WMO
4680 SYNOP code
reference)
Fixed
Block
10
8
1
ElecFld
Electric Field
int16
Vm
R
Fixed
Block
11
9
1
SurWet
Surface
Wetness
int16
k
Ω
R
Fixed
Block
12
10
1
SoilWet
Soil Wetness
int16
Pct
R
PVMET-500HOLDING REGISTERS
A complete table of all the SunSpec holding registers is shown in the appendix.
The PVmet
500’s
first register C SunSpec ID is located at 40,001. This document assumes base 1 addressing is being used. If the host
system uses base 0 addressing, decrement the starting register values shown by 1.
All registers in the SunSpec Register map are read-only. Use the Modbus 03 command to access the data. Do not attempt to read
beyond the specified map, the PVmet-500may not respond.
SCALING
Holding registers only support integer values (no decimal points). To improve resolution many of the measured values are scaled up by
a factor of 10 or 100. The Modbus master must convert the data point to a floating-point variable and multiply by the “scale factor”
indicated in the table below. For example, a temperature of 25.3°C will be reported as 253. Multiplying by the scale factor of 0.1 results
in a final value of 25.3.
RAINFALL OPERATION
The SunSpec specification for rainfall mandates that the rainfall register 40 077 will reset after each Modbus poll. To effectively use
this parameter, the host system must implement a separate running rainfall counter variable in the host system. The contents of the
rainfall register must then be added to this variable on EVERY read. As this may be difficult to implement on many systems a second
register has been provided outside the SunSpec register map. The separately provided value is a running counter in mm.