GOLF TECHNICAL BULLETIN

 

 

 

 

Rain Bird Confidential - GTB #21-01 

Date: December 21, 2011 

 

Rain Bird Corporation 

Golf Division 

6991 E. Southpoint, Tucson, AZ 85706  (800) 984-2255 Fax: (520) 741-6522

 

*NOTE – This correspondence is being delivered to golf sales managers at Rain Bird Corporation’s Golf Division 
authorized distributor organizations.  Please distribute to your team at your discretion.  Thank you. 

 
 

New Wiring Instructions for AG2401c3 Intermatic Surge Arrestor on Rain 

Bird PAR+ES Controller 

 
 

The Intermatic AG2401c3 surge arrestor was introduced a year ago replacing the AG2401 which is 
discontinued.  Based on design changes made by Intermatic the wiring instructions in our PAR+ES 
Installation Manual, which were specific to the AG2401, no longer apply to the AG2401c3 and must not 
be used. Failure to wire the surge arrestor properly will not adequately protect the controller against 
surge damage. 
 
The AG2401c3 must be wired as indicated below in order to function properly. In all cases the 
instructions provided by the supplier, Intermatic should be followed. The green LED on the device will 
indicate that the wiring was done correctly and the surge arrestor is operational. 
 

Follow the instructions in the PAR+ES 
Installation Manual to mount the surge 
arrestor to the junction box as shown in 
the picture below. 

Run the three wire leads from the 
surge arrestor, two black and one 
white, into the junction box. 

- For 

120 VAC installations

, connect 

the two black wires from the surge 
arrestor to the HOT (black) power wire. 
Connect the white surge arrestor wire 
to the NEUTRAL (white) power wire. 

- For 

220/240 VAC Single Phase –

Three-wire (Black, Red and Green) 
installations

, connect one black wire 

from the surge arrestor to the HOT 
(black) power wire, and the other black 
wire to the other HOT (red) power wire. 
Connect the white surge arrestor wire to the EQUIPMENT GROUND (green) power wire. 

- For 

220/240 VAC Single Phase – Four-wire (Black, Red, White and Green) installations

connect one black wire from the surge arrestor to the HOT (black) power wire, and the other 
black wire to the other HOT (red) power wire. Connect the white surge arrestor wire to the 
NEUTRAL (white) power wire. 

 
 