ESP-LXIVM Controller Troubleshooting Guide
ORANGE
ORANGE
ORANGE
ORANGE
Terminal Block
on LX-IVM
(24VAC IN)
LX-IVM Transformer
(26.5VAC Out)
Choke: Schaffner
P/N: RD5122-6-9M6
Capacitor, Kemet P/N:
C274ACF5100SA0J
BLUE
GREEN or GREEN YEL.
(not connected)
GROUND
* Contact Rain Bird GSP for
assistance with sourcing
Choke and Capacitor
Components
VFD Filter Connection
Connecting a VFD Pump in the same power circuit as the LX-IVM Controller
makes it prone to electrical noise having undesirable behavior. Symptoms
can include inconsistent operation of the stations and inability read flow
from a compatible flow sensor. Rain Bird recommends the following
modification to the controller to “filter out” the noise from the VFD and
ensuring normal operations of the Controller.
YELLOW
BROWN
YELLOW