background image

 

889-3809-02 

Model 2018E Operations Manual Rev Apr 2020                Page 

8

 of 39 

2.4.10

 

FACTORY SETTINGS 

The monitor is configured at the factory during final test.  Data set at the factory includes:  Model Number, Serial 
Number, Manufacture Date, Real Time Clock setting, Support for Flashing Greens, Fast Start-Up, Lower AC 
Power Thresholds, LA DOT configuration, NYS DOT configuration, and support for a Diagnostic LCD.  The Up 
Time Accumulator is initialized to zero prior to final testing.  Changes to any of the factory options are logged in 
the configuration log. 

2.4.11

 

USER UNIT INFORMATION 

The monitor has non-volatile memory that can be used to store the following user unit information: 40 character 
Location ID, 4 character Unit ID, and 5 character Agency ID.  All of these IDs can consist of any alpha-numeric 
characters.  Upper and lower case characters can be used. 

2.5

 

FAULT MONITORING 

2.5.1

 

CONFLICT MONITORING 

Configuration:

  The diodes removed on the Program Card determine permissive (non-conflicting)  channels.  

Removal of the diode labeled “2-6” would make Channels 2 and 6 permissive with each other.  This is a two-way 
relationship.  If channel 2 is programmed as permissive with channel 6 then channel 6 is automatically permissive 
with channel 2.  The testing defaults for this feature are determined by the diodes removed on the program  card.  
Typically no diodes are removed during automated testing. 

Test Preformed:

  While a channel has a Green or Yellow display active, the channel is tested to see if a non-

permissive channel has a Green or Yellow display active at the same time.  If concurrently active conflicting 
displays are detected a conflict timer is started.  If the conflict goes away, the conflict timer is stopped (it is not 
cleared) and a non-conflict timer is started.  If the conflict reappears the non-conflict timer is reset to zero and the 
conflict timer continues timing from its prior value.  If the conflict timer reaches 333 milliseconds or more the 
monitor will latch a conflict fault.  If the non-conflict timer reaches 666 milliseconds the conflict timer is reset to 
zero and the conflict is ignored.  The normal voltage thresholds for this test are: Reds – ON when above 70V

RMS

 

and OFF when below 50V

RMS

, Greens and Yellows – ON when above 25V

RMS

 and OFF when below 15V

RMS

Fault Action:

  The monitor transfers the Output relay contacts to the fault condition, activates the Stop Time 

output, and illuminates the 

CONFLICT

 indicator on the front panel.  The Signal Sequence log and the Prior Faults 

log will record this fault. 

Resetting the Fault:

 The monitor remains in this fault condition until the unit is reset by the activation of the front 

panel reset pushbutton or the activation of the reset input.  Power loss or power interruption will not reset this fault.  
The Reset log will record the resetting of this fault. 

Modifying Inputs:

 

 

MC Coil (Relay Output, Side 2)

: If Flashing Don’t Walk Monitoring is enabled and channels have 

been programmed as active channels, flashing don’t walk conflict testing will not be performed when 
this input is below 50V

RMS

 and will be performed when this input is above 70V

RMS

Feature Interactions: 

Yellow Disable Jumpers

: When Yellow Disable is jumpered for a channel that Yellow is removed 

from all conflict testing. 

Flashing Don’t Walk Monitoring

: When Flashing Don’t Walk Monitoring is enabled and channels 

have been programmed as active, a flashing red on a channel with this feature active will be included 
in the displays checked for conflicts.  A conflict with a flashing red must exist for 1500 milliseconds 
to create a conflict fault. 

Flashing Yellow Arrow Left Turns

: When Flashing Yellow Arrow (FYA) Left Turns are enabled and 

FYA Ignore Yellow Conflict is enabled and a Channel has an FYA checked as a child channel that 
conflicts with this channel, a Yellow in that channel (if it is terminating a Flashing Yellow Arrow) and 
a Yellow in the child channel being active at the same time will be ignored as a conflict.  Also, if a 
display is a Flashing Yellow Arrow it must flash.  If it does not flash the monitor will remove the 
permissive with the programmed opposing channel thus causing a conflict with the Green or Yellow 
of the opposing channel if they are on. 

LED Thresholds

: When LED Thresholds is enabled the monitor senses Greens, Yellows, and Reds as 

ON when their voltage is above 25V

RMS

 and OFF when below 15V

RMS

 for the conflict test. 

2.5.2

 

RED FAIL MONITORING 

Configuration

:  All channels with a setting of “ON” for Red Fail switches will be monitored for the red fail fault.  

The testing defaults for this feature are all channels enabled for red fail testing. 

Test Preformed

: When a channel has no displays active (Red, Yellow, or Green) a red fail timer is started.  If a 

display turns on for the channel the red fail timer is stopped (it is not cleared) and a non-red fail timer is started.  If 

Содержание 2018E

Страница 1: ...ntains technical information for the Model 2018E Conflict Monitor pn 889 3809 02 Revision April 2020 Model 2018E Conflict Monitor Firmware Version 01 05 01 Operations Manual Caltrans TEES 2002 Conflic...

Страница 2: ......

Страница 3: ...BLICATION REPRODUCTION OR USE IN WHOLE OR PART IS NOT PERMITTED EXCEPT UNDER TERMS AGREED UPON IN WRITING ALL REGISTERED TRADEMARKS OF EBERLE DESIGN INC ARE UNDER COPYRIGHT MAINTENANCE NOTE IT IS AN E...

Страница 4: ......

Страница 5: ...emperature Sensor 7 2 4 7 Real Time Clock 7 2 4 8 Up Time Accumulator 7 2 4 9 Configuration Monitoring Beeping Monitor 7 2 4 10 Factory Settings 8 2 4 11 User Unit Information 8 2 5 Fault Monitoring 8...

Страница 6: ...2 7 2 Monitor Reset Log 21 2 7 3 Configuration Event Log 21 2 7 4 Prior Faults Log 21 2 7 5 AC Line Log 21 2 7 6 Signal Sequence Log 21 2 8 Diagnostics 22 2 8 1 Memory 22 2 8 2 Microprocessor Monitor...

Страница 7: ...ndicator 33 4 2 5 CONFLICT Indicator 33 4 2 6 RED FAIL Indicator 33 4 2 7 MULTI IND Indicator 33 4 2 8 YELLOW Indicator 33 4 2 9 PC AJAR Indicator 33 4 2 10 DIAG FAIL Indicator 33 4 2 11 COMM Indicato...

Страница 8: ......

Страница 9: ...escent field display thresholds 2010 Monitor timings with 16 Channels using LED field display thresholds 2010 Monitor timings with 18 Channels using LED field display thresholds The differences betwee...

Страница 10: ...nection terminals in the Controller Assembly For the purpose of conflict determination a signal on any of the Green or Yellow inputs associated with a channel shall be considered as that channel being...

Страница 11: ...nal input is measured approximately 13 000 times per second to provide an accurate true RMS root mean square AC voltage regardless of distortions in the waveform or changes in line frequency Both posi...

Страница 12: ...on 2 to function Typical Connection Unterminated or Preemption circuitry 2 1 7 MC COIL INPUT The monitor provides an input to monitor the state of the Mercury Contactor MC Coil Rear Edge Connector Pin...

Страница 13: ...less When operating in the 2010 mode prior to the monitor transferring the Output relay contacts from the Fault state to the No Fault state a transition state with a duration of 250 milliseconds occu...

Страница 14: ...56 0 Hz or greater than 64 0 Hz The hysteresis from the OFF state to the ON state or vice versa is at least 3VRMS and the line frequency hysteresis is at least 1 0 Hz If the factory option for Low AC...

Страница 15: ...Real Time Clock is initialized to local Pacific Standard Time when the unit is undergoing final test In addition the Daylight Saving Time user option is set to Off The Real Time Clock is preprogrammed...

Страница 16: ...utput relay contacts to the fault condition activates the Stop Time output and illuminates the CONFLICT indicator on the front panel The Signal Sequence log and the Prior Faults log will record this f...

Страница 17: ...f a Flashing Yellow Arrow channel the Yellow will still be used in the parent channel s red fail test regardless of the Yellow Disable jumper setting of the child channel 2010 Mode When the 2010 mode...

Страница 18: ...en of the child channel will be included in the dual indication test for that channel If a Channel has an FYA setting with a yellow border for one of its child channels then the Yellow of the child ch...

Страница 19: ...performed on all channels Test Preformed When a channel has a Green that turns off a conflicting channel cannot display a Green or Yellow for at least 2 7 seconds When each Green turns off a 2 7 seco...

Страница 20: ...formed The Watchdog Timer input Rear Edge Connector Pin 22 is monitored A voltage of less than 4VDC is recognized as a low and a voltage greater than 12VDC is recognized as a high The input must chang...

Страница 21: ...m the flashing state to the solid on state and not falsely trip Typical Use This feature is used to provide additional fault checking for Flashing Don t Walk displays on pedestrian channels Without th...

Страница 22: ...ting with a green or yellow border for one of its child channels then the Yellow of the parent channel will be used for terminating the Yellow or Green of the child channel and will be checked for sho...

Страница 23: ...Indication Monitoring The testing default for this feature should be disabled Operations Modified Dual Indication Monitoring When the Dual Enable switch is OFF for a channel and Green Yellow monitori...

Страница 24: ...hort Yellow testing senses Greens Yellows and Walks as ON when their voltage is above 25VRMS and OFF when below 15VRMS Reds are ON when their voltage is above 70VRMS and OFF when below 50VRMS With LED...

Страница 25: ...ADIAN FAST FLASH Configuration This is a factory option and cannot be changed by the user If this function is required but it is not active contact Reno A E Technical Support for assistance This featu...

Страница 26: ...og When Log Field Changes is enabled the Signal Sequence log will change from recording the state and voltage on every input every 33 milliseconds to checking every 33 milliseconds to see if the state...

Страница 27: ...annel 10 Green driving the flashing yellow arrow for the channel 7 left turn 2 6 4 3 FYA FOR CHANNELS 5 18 USE YELLOW DRIVERS FYA 5 18 USES YEL Configuration This feature is only effective if Flashing...

Страница 28: ...e Yellow arrow parent channel Yellow used to terminate a flashing Yellow arrow and the Yellow of the conflicting child normally the opposing through Yellow ball will be ignored If the Yellow arrow is...

Страница 29: ...te historical record of cabinet operation When the date and time are not available through Port 1 the monitor will use its internal Real Time Clock as a date time stamp for events 2 7 1 TIME CHANGE LO...

Страница 30: ...ostic failure is not reset by a monitor Power Failure 2 8 1 MEMORY The monitor verifies all memory elements on power up or upon reset of a Diagnostics failure A failure of any of the memory tests will...

Страница 31: ...mount of time DC Processor Timeout 6 0020h The DC processor did not respond to a request for data in the required amount of time Temperature Timeout 7 0040h The temperature sensor did not respond to a...

Страница 32: ...AC VOLTAGE INPUTS Normal AC Power Thresholds Dropout 98VRMS Restore 103VRMS Low AC Power Thresholds Dropout 92VRMS Restore 98VRMS AC Line Frequency Dropout 56Hz or 64Hz Restore 57 5Hz and 62 5Hz MC C...

Страница 33: ...l 350 ms FLASHING DON T WALK No Fault 1400 ms Respond 1600 ms Typical 1500 ms Flashing if state changes are 200 ms and 600 ms Typical 500 ms 2010 MODE OF OPERATION 24 VDC LOW No Fault 200 ms Detect 50...

Страница 34: ...n I L Channel 7 Yellow I 11 Channel 14 Yellow I M Channel 3 Green I 12 Channel 3 Yellow I N Channel 16 Yellow I 13 Channel 9 Green I P Channel 17 Yellow I 14 Channel 17 Green I R Channel 10 Green I 15...

Страница 35: ...O x x 5 Channel 13 Red I 4 Ground 6 Special Function 2 I 7 Channel 12 Red I 8 Special Function 1 I 9 Channel 10 Red I 10 Channel 11 Red I Ethernet Connector 11 Channel 9 Red I Pin Function 12 Channel...

Страница 36: ...11 Green 12 Channel 13 Green N Channel 12 Green 13 Channel 14 Green P Channel 13 Green 14 Channel 15 Green R Channel 14 Green 15 Channel 16 Green S Channel 15 Green 16 Programming Card Ajar T Program...

Страница 37: ...Mini USB Port Mini USB Port for communications with Laptop or Modem Field Status LEDs One LED for each field input All field status LEDs are latched if a fault occurs Field inputs that caused the fau...

Страница 38: ...t flashing Don t Walk displays to not conflict with other greens or yellows at the intersection In order to use this feature the RaeComM software must be used to set the channels that this feature is...

Страница 39: ...if the RED ENABLE input is not active The GY Dual Indication Monitoring enable can be used in conjunction with the DUAL ENABLE switches on the circuit board Channels that have their DUAL ENABLE switch...

Страница 40: ...ed every 16 milliseconds by the monitor 4 2 1 FIELD STATUS INDICATORS There are 54 field status indicators one for each field input The display is logically organized into three columns and eighteen r...

Страница 41: ...icate that a Short Yellow or Short Clearance fault has been detected on the field inputs See Section 2 5 4 for more information on a Short Yellow fault and Section 2 5 5 for more information on a Shor...

Страница 42: ...ion change is identified the monitor will enter a configuration fault mode and the audible buzzer will start to beep at a one second rate This is an indication that a change to the current configurati...

Страница 43: ...display mode While in the diagnostic display mode a short press of the front panel RESET pushbutton will advance to the next diagnostic display The diagnostic display sequence is Tap RESET to move be...

Страница 44: ...Disable jumpers installed and Dual Indication is enabled for all channels 4 4 2 1 PERMISSIVE DISPLAYS The left display is the ID Display P1 The right display is the Data Display On the Data Display F...

Страница 45: ...onitoring and the feature is enabled Flashing Yellow Arrow monitoring is enabled 2010 mode of operation is selected LED Thresholds are enabled Watchdog switch is set to enabled Flashing Yellow Arrow I...

Страница 46: ...ally displaying the fault All LEDs except AC POWER and COM are displayed in the same state as they were when the prior fault occurred If the display reverts back to AC Line Voltage while trying to acc...

Страница 47: ...th the monitor to be upgraded by clicking on IDENTIFY in the menu and observing that the monitor is correctly identified by the program 6 On the CONFIG menu choose UPGRADE FIRMWARE 7 On the Code Loade...

Отзывы: