ACCESS
Door Profile
32207C 3/97
D9210B Program Entry Guide
© 1997 Radionics
Page 4
DOOR PROFILE
This programming category is used to:
•
Assign an area which also activates the D9210B
•
Assign a point to the door
•
Program the door state to change when the arm state changes
•
Allow for the strike relay to activate upon a fire alarm
Door #
Default:
1
Selections:
1 - 8
Enter the number of the door you are about to program.
NOTE: The D9412 supports 8 doors; the D7412 supports 2 doors.
D# Entry Area #
Default:
Blank
Selections:
Blank, 1 - 8
Assign an area to the door controller. This entry allows the D9210B to be polled
activating communication to the panel. This also is the area a user will exit
when initiating a request to exit (REX).
1 - 8 -------- The area assigned to the door controller to which the reader will
allow access.
Blank ------ Door controller will not function.
NOTE: All SDI devices, regardless of area assigned, will report to Area 1,
Account 1 by default upon SDI failure. If a D9210B becomes disconnected,
an SDI Fail ## and a MISSING POINT ### event will be created.
Programming Tip: [9210 NOT READY] will appear at this command
center when you press the ENTER key if the D9210B is not programmed
with a D# Entry Area.
D# CC# Scope
Default:
Blank
Selections:
Blank, 1 - 8
Enter the Command Center number (CC#) which determines the scope of the
user ID’s disarming rights. Areas will disarm on the basis of this Command
Center’s scope and the Authority Level of the user.
1 - 8 -------- This CC# Scope determines disarming rights. The user’s access
level in conjunction with the CC # Scope will determine which areas
will be disarmed.
Blank ------ Only the area assigned to the D# Entry Area will disarm for this
door.