32206C 3/97
D9210B Operation & Installation Manual
© 1997 Radionics
Page 16
Step 12: Programming and Activating the D9210B
Description. The D9210B needs to be assigned with an area before it will
communicate properly with the panel. In addition, the dipswitch settings and the
power need to be connected.
The dipswitch settings in Table 4 determine the address of the D9210B. At the
top of the ACCESS program record sheet, the address number (noted next to
the dipswitch setting in Figure 4) will determine which parameters for the door
controller are sent.
To activate the D9210B, follow the instructions in the D9210B Program Entry
Guide (32207). Use the ACCESS Program Record Sheet (32208) to match the
door to the proper address and to ensure that the door is assigned to the proper
area.
Step 13: Testing the D9210B
Description. The D9210B comes shipped with a default program that will let you
run a quick test upon installing the unit. Go through the following items to verify
the D9210B is functioning properly. If you have problems, see the trouble
shooting section.
D9210B: Verify that the Operational Monitor LED is pulsing approximately once
every second. This indicates the microprocessor is running. Go to the [UNLOCK
DOOR] function. A number from 1 to 8 should appear for the door controller. If
an “F” appears, the unit has failed.
Zone: Using the Control Center, verify the point is normal when the door is
closed, the point goes off normal when the door is opened and a shunt is not
applied, and that the point stays normal upon opening the door on a valid access
granted.
Strike: Read a valid token to activate the strike. If tokens have not been added,
use the [DOOR CONTROL], [DOOR UNLOCK] mode to cycle the strike. In
addition, you will cycle the strike when you test the RTE/REX inputs (if shunt only
is not yes).
RTE/REX: Fault these inputs to activate the strike. The default for the strike time
is 10 seconds. Test each separately.
Buzzer: The buzzer should have sounded on each strike activation. Also hold
the door open past the normal shunt time and ensure the “Extend Buzz”
functions.
Reader: The reader LED will be red upon powering up the D9210B. During the
above tests, it will turn green anytime the strike is activated.
To verify the reader, check and see that the D1 and D0 LED’s blink rapidly while
a card is passed through the reader or a token is held up to the proximity reader.
For other LED functionality, see Table 5, “LED Troubleshooting” .
www.PDF-Zoo.com
firealarmresources.com