32206C 3/97
D9210B Operation & Installation Manual
© 1997 Radionics
Page 14
Step 10: Setting the Dipswitch and Tagging the Unit
The D9412 panel supports up to eight door controllers using all eight address
settings. The D7412 supports up to two door controllers using the first two
address settings. Each D9210B uses one of eight addresses. Addresses can
not be duplicated. Because the D9210B is always supervised, two D9210B
modules having the same address will not function and SDI failures will occur.
Fill out the Program Record Sheet. Be sure the program record sheet for this
door controller contains the area assignment, address assignment and control
center assignment.
TECH TIP: Whenever possible, be consistent when numbering doors, control
centers, and areas. This will help when programming a system with more than
one door. (Example: Assign Door 1 to Area 1 and Control Center 1.)
The D9210B dipswitch with factory default
settings (all ON) is shown in Figure 4. Table 4
shows the serial device reporting address
settings for each door controller. Table 4 also
shows dipswitch settings for Test and Fail
modes.
Door Controller Address
Fail
Mode
Test
Mode
Memory
Dump
1
2
3
4
5*
6*
Serial Device
Control Center
Display
Central Station
Modem IIIa
2
D9210 #1
SDI #33
ON
ON
ON
---
---
---
D9210 #2
SDI #34
OFF
ON
ON
---
---
---
D9210 #3
SDI #35
ON
OFF
ON
---
---
---
D9210 #4
SDI #36
OFF
OFF
ON
---
---
---
D9210 #5
SDI #37
ON
ON
OFF
---
---
---
D9210 #6
SDI #38
OFF
ON
OFF
---
---
---
D9210 #7
SDI #39
ON
OFF
OFF
---
---
---
D9210 #8
SDI #40
OFF
OFF
OFF
---
---
---
SDI Fail Mode
SDI Fail – Door Unlocked
---
---
---
ON
---
---
SDI Fail – Door Locked
---
---
---
OFF
---
---
* Switches 5 and 6 must stay in the “ON” position.
Table 4. D9210B Dipswitch Settings
Figure 4. D9210B DIP Switch
(Factory Settings)
www.PDF-Zoo.com
firealarmresources.com