D9000/D7000 Series Operation & Installation Manual
Page 61
74-07692-000-C 4/97
Current Rating Chart for Standby Battery Calculations
A
B
C
AC Power On
Normal Current
AC Power Off
Minimum Current
In Alarm
Maximum Current
Model
Number
Quantity
Used
Each
Unit*
Total
Each
Unit
Total
Each
Unit
Total
D9412/D9112/
D7412/D7212
______
350
x 1 = 350
350
x 1 = 350
500
x 1 = 500
D125B
______
20 x
Quant.
= ____
19 x
Quant.
= ____
123 x
Quant.
= ____
D127
______
13 x
Quant.
= ____
12 x
Quant.
= ____
45 x
Quant.
= ____
D129
______
25 x
Quant.
= ____
25 x
Quant.
= ____
25 x
Quant.
= ____
D185
______
120 x
Quant.
= ____
120 x
Quant.
= ____
350 x
Quant.
= ____
D192D
______
15 x
Quant.
= ____
26 x
Quant.
= ____
50 x
Quant.
= ____
D192C
______
15 x
Quant.
= ____
26 x
Quant.
= ____
50 x
Quant.
= ____
D1255
______
104 x
Quant.
= ____
106 x
Quant.
= ____
206 x
Quant.
= ____
D1256
______
104 x
Quant.
= ____
106 x
Quant.
= ____
206 x
Quant.
= ____
D1257
______
104 x
Quant.
= ____
106 x
Quant.
= ____
206 x
Quant.
= ____
D720
______
55 x
Quant.
= ____
20 x
Quant.
= ____
75 x
Quant.
= ____
D8125
______
48 x
Quant.
= ____
48 x
Quant.
= ____
48 x
Quant.
= ____
D8127T/U
______
3 x
Quant.
= ____
3 x
Quant.
= ____
4 x
Quant.
= ____
D8128C
______
50 x
Quant.
= ____
50 x
Quant.
= ____
50 x
Quant.
= ____
D8129
______
20 x
Quant.
= ____
20 x
Quant.
= ____
20 x
Quant.
+ (25 x
# of relays
) = ___
D8130
______
5 x
Quant.
= ____
5 x
Quant.
= ____
54 x
Quant.
= ____
D9127T/U
______
0.5 x
Quant.
= ____
0.5 x
Quant.
= ____
0.8 x
Quant.
= ____
D9131A
______
24 x
Quant.
= ____
22 x
Quant.
= ____
36 x
Quant.
= ____
D9210B
______
100 x
Quant.
= ____
100 x
Quant.
= ____
120 x
Quant.
= ____
D928
______
14 x
Quant.
= ____
14 x
Quant.
= ____
45 x
Quant.
= ____
Ratings of other devices in the system which are not shown above:
________
______
____ x
Quant.
= ____
____ x
Quant.
= ____
____ x
Quant.
= ____
________
______
____ x
Quant.
= ____
____ x
Quant.
= ____
____ x
Quant.
= ____
________
______
____ x
Quant.
= ____
____ x
Quant.
= ____
____ x
Quant.
= ____
________
______
____ x
Quant.
= ____
____ x
Quant.
= ____
____ x
Quant.
= ____
________
______
____ x
Quant.
= ____
____ x
Quant.
= ____
____ x
Quant.
= ____
Total A = _____
Total B = _____
Total C** = _____
NOTES:
* Currents shown in milliamperes (1 ampere = 1000 milliamperes)
** If the column C total exceeds 1400 mA, a D8132 is required to provide an additional 1400 mA. You may
also use a UL listed external power supply for this purpose.