D9000/D7000 Series Operation & Installation Manual
Page 13
74-07692-000-C 4/97
Instructions for wiring the off-board point POPIT
sensor loops are found in the instructions
packaged with the POPIT modules.
Install Modules and Relays
1.
Power Down First: Power down the unit by
unplugging the transformer and
disconnecting the battery. Radionics
recommends that you power down the unit
when installing modules or relays, or when
making wiring connections to the panel.
2.
Install and wire any modules required for
your installation as described in the
module’s installation instructions.
Instructions for the D8125 POPEX Module,
the D8128C OctoPOPIT Module, the D8129
OctoRelay Module, the D811 Arm Status
Relay Module, and the D928 Dual Phone
Line Switcher appear in this manual.
See
Off-board Points for D8125 and D8128C
instructions. See
Relays for D8129 and
D811 instructions. See
Dual Line
Transmitting in the Telephone Connections
section for instructions for the D928.
3.
If you are using the power outputs at
terminals 7 or 8, install a D136 relay in the
appropriate sockets. See
Programmable
Power Outputs in the Power Outputs section
for instructions.
4.
If you are using a ground start phone system,
insert a D136 relay in socket K6/J5 and set
the ground start pin in the ground start
position. See
Ground Start in the Telephone
Connections section.
Make the Telephone Connections
See
Telephone Connections. If you are
connecting the panel to a ground start phone
system, you need to install D136 relay, see
Install
Modules and Relays above.
Connect the On-Board Points and Command
Centers
Connect the on-board points and Command
Center wiring to the system. See the
On-Board
Points and Arming Devices sections for
instructions.
Power Up
Reconnect the battery and then plug in the
transformer. Remember the buzzer sounds for 2
seconds when you first power up the panel.
Leave the reset pin locked down for now.
Yellow Charging Status LED doesn’t go out: If
the yellow charging status LED doesn’t go out
within 5 minutes of powering up the panel, the
battery may be deeply discharged, or you may
have connected too many powered devices to
the panel. Combined continuous current draw for
terminals 3, 8, 24, and 32, the Accessory
Connector (J2), and the Expansion Port (J4)
cannot exceed 1.4A. See the
Power Outputs
section for help.
Programming the Panel
If you haven’t created a program for the panel,
review the
D9000/D7000 Series Program Entry
Guide (74-07695-000). Check to be certain you
have all the required accessory modules
installed for the features you want to use. The
reset pin must be in the locked position to copy or
send information to and from the panel.
Use the D5200 Programmer or the Remote
Account Manager (RAM III) to load your custom
program into the panel.
Move the reset pin to the normal position. See
Figure 3. The panel transmits reboot and battery
reports to the receiver if programmed for
reporting.
Install the Point Chart Label
Radionics recommends you fill out the
Point
Chart Label (79-06660-000) provided in the
literature pack and install it on the inside of the
enclosure door for all systems.
Point chart label required for fire systems with
verification points: You must install the point
chart label for fire or combined fire/burglary
systems using verification points.
Use the program record sheet to gather the
information you need to fill out the point chart.
Install the label on the enclosure door as shown
in Figure 2. To avoid smearing your entries on
the chart, use the label's peel off backing to press
the label in place.