A weak chimney is the main reason for having a smoke on the upper or
lower door, especially at higher fan speeds during the ignition or during
operation of the boiler.
If there is too much smoke on the door and in the boiler room during
the ignition of the boiler, or the flue gas temperature does not rise enough for
the boiler to start operating and all because of the insufficiently strong
chimney, it is technically justified to remove the wire turbulators from the pipe
exchanger.
3.4. Dedusting
Dedusting implies the automatic cleaning of the boiler from soot by using compressed air. In
order to achieve effective dedusting, it is necessary to do the whole installation by following
regulatory standards for this area. It is necessary to select an appropriate compressor, provide
quality air, and the appropriate amount of air to run a valve which insert air under pressure into
the boiler.
The entire system is comprised of three units as seen in Picture 6:
Picture 6. Dedusting system
-
UNIT A -
compressor unit
-
UNIT B
– rezervoar vazduha*
-
UNIT C
- otprašivačka jedinica
Unit A:
Obtained by a buyer.
In order to validate the warranty issued by a seller, it is necessary to acquire the
compressor unit that meets the following conditions:
-
The compressor has to have minimum airflow of 200 L/min