1. INSTALLATION
INST
ALLER
· permanent openings on the external walls of
the location (windows);
· single or collective, ramified ventilation ducts.
The openings on the external walls of the location
must respect the following requirements:
· have a net overall free passage section of
at least 6 cm
2
for every kW of heat capacity
installed with a minimum of 100 cm
2
;
· they must be realized so as to make sure that
the opening inlets are not obstructed (neither
indoors nor outdoors);
· they must be protected with grids, metal
meshes, etc. so as to keep the useful section
mentioned above.
· they must be placed at a height next to the
floor level such as to allow proper operation of
the combustion products discharge systems;
if such position can not be obtained, please
increase by at least 50% the section of the
vents.