Start IP
Default = IP address of ETH int 1
DHCP Server assigns addresses to connected clients starting from this address.
End IP
DHCP server assigns IP addresses to clients from the range defined by Start IP and End IP
(inclusive).
No of leases
Default = 5 [1 - 255]
Maximum number of DHCP client(s) which can RipEX simultaneously serve. It can not be more
than the number of addresses available in the Start IP - End IP range.
Lease timeout [DD:HH:MM:SS]
Default = 1 day (max. 10 days)
A DHCP Client has to ask DHCP Server for refresh of the received configuration within this
timeout, otherwise the Lease expires and the same settings can be assigned to another device
(MAC).
Assigned IPs
Table shows MAC addresses of Clients and IP addresses assigned to them by the Server. Ex-
piration is the remaining time till the respective Lease expires. If the assigned IP addresses are
required to be deleted, set DHCP Server to Off, then action Apply and set DHCP server to On
(+Apply) again.
Preferred IPs
It is possible to define which IP should be assigned by the Server to a specific MAC. The reques-
ted IP has to be within the Start IP – End IP range.
■
Shaping*
List box: On, Off
Default = Off
Ethernet interface could easily overload the Radio channel. Because of that, it is possible to shape
traffic received from the ETH interface.
If "On", specified volume of
Data [Bytes]
in specified
Period [s]
is allowed to enter the RipEX from
ETH interface. The first packet which exceeds the limit is stored in the buffer and transmitted when
new Period starts. Further over-limit packets are discarded.
■
Speed
List box: Auto, 100baseTX/Full, 100baseTX/Half, 10baseT/Full, 10baseT/Half
Default = Auto
Communication speed on the Ethernet interface.
■
Modbus TCP*
Use this setttings only for
Modbus TCP Master
when it communicates with both types of Modbus
slaves using either Modbus RTU or Modbus TCP protocols. Or when TCP/IP communication should
run locally between Modbus Master and RipEX in Modbus TCP network. Read Help and Application
note Modbus in RipEX.
For more information refer to the manual Application note / Modbus TCP
1
.
1
http://www.racom.eu/eng/products/m/ripex/app/modbus.html
135
© RACOM s.r.o. – RipEX Radio modem & Router
Advanced Configuration
Содержание RipEX
Страница 2: ......
Страница 42: ... DQ Data Quality Min 180 PER Packet Error Rate Max 5 RipEX Radio modem Router RACOM s r o 42 Network planning ...
Страница 222: ...Fig 10 3 ATEX Certificate RipEX 2 3 RipEX Radio modem Router RACOM s r o 222 Safety environment licensing ...
Страница 223: ...Fig 10 4 ATEX Certificate RipEX 3 3 223 RACOM s r o RipEX Radio modem Router Safety environment licensing ...