INSTRUCTIONS
T5HE/U6 & DRIVER TYPE C
and end users to save energy. We’d love to hear your comments. Please call the Marketing Department at 888-RAB-1000 or email: [email protected]
•
READ CAREFULLY BEFORE INSTALLING LAMPS. RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE.
required for safety. THIS PRODUCT MUST BE INSTALLED IN ACCORDANCE WITH THE APPLICABLE INSTALLATION CODE BY A PERSON
FAMILIAR WITH THE CONSTRUCTION AND OPERATION OF THE PRODUCT AND THE HAZARDS INVOLVED.
WARNINGS:
•
•
•
Risk of fire or electric shock. LED Retrofit Kit installation requires knowledge of luminaire electrical systems. Installation
should be performed only by a qualified electrician in accordance with the National Electrical Code and relevant local code.
Risk of fire or electric shock. Install this kit only in the luminaires that have the construction features and dimensions shown
in the photographs and/or drawings and where the input rating of the retrofit kit does not exceed the input rating of luminaire
• Only those open holes indicated in the photographs and/or drawings may be made or altered as a result of kit installation.
Do not leave any other open holes in an enclosure of wiring or electrical components.
To prevent wiring damage or abrasion, do not expose wiring to edges of sheet metal or other sharp objects.
• Risk of fire or electric shock. Luminaire wiring and electrical parts may be damaged when drilling for installation of LED
retrofit kit. Check for enclosed wiring and components.
T5HE-10-24P-8XX-EXT
T5HE-11-36P-8XX-EXT
T5HE-13-48P-8XX-EXT
T8-15-U6GC-8XX-EXT
Model Number
Maximum Lamps in Luminaire
Lampholder-to-Lampholder Spacing
Length
Width
Heigth
Lamp Compartment
Dimensions
CAUTION
Check the Max. case temperature of the fluorescent lamp ballast before replacement. The temperature shall be below or
equal to the maximum case temperature (194
/90
) of the external driver. The external driver shall be mounted at the
same location as the ballast.
• Disconnect power at the source before installation, inspection or removal. Do not simply switch off fixture.
• This item is rated at 120-277V. Installer must determine whether line voltage 120-277V is available at the luminaire before
installation.
• Not intended for use with emergency exit fixtures or emergency exit lights.
• Do not use if product is damaged.
• Suitable for use with shunted and non shunted lamp holders.
• Do not make or alter any open holes in an enclosure of wiring or electrical components during kit installation.
• Risk of fire or electric shock. Do not open or modify. No user serviceable parts inside.
• SUITABLE FOR “TYPE IC” OR “TYPE NON-IC” LUMINAIRES.
• No external weight or mechanical force should be applied to tube or components.
• THE RETROFIT ASSEMBLY IS ACCEPTED AS A COMPONENT OF A LUMINAIRE WHERE THE SUITABILITY OF THE COMBINATION
SHALL BE DETERMINED BY UL OR AUTHORITIES HAVING JURISDICTION.
• SUITABLE FOR DRY AND DAMP LOCATIONS ONLY.
• Complies with Part 15 of FCC. Operation is subject to the following two conditions: (1) This device may not cause harmful
interference, and (2) This device must accept any interference received including interference that may cause undesired
operation.
• Installers should not disconnect existing wires from lamp holder terminals to make new connections at lamp holder
terminals. Instead installers should cut existing lamp holder leads away from the lamp holder and make new electrical
connections to lamp holder lead wires by employing applicable connectors.
• “This luminaire has been modified to operate RAB LIGHTING T5 EXT LED lamps” shall be marked on the retrofit luminaire
where readily visible by the user during normal maintenance including re-lamping.
• RAB LIGHTING T5 EXT tubes and drivers are sold separately. This lamp is DC input. Do not operate LED tubes without
corresponding compatible driver (refer to compatibility table below).
IMPORTANT
lamps
The minimum lamp compartment dimensions are described below:
•
•
DRI-30T5HE-2L-DIM
DRI-60T5HE-4L-DIM
F
C
T5HE-10-24P-8xx-EXT
T5HE-11-36P-8xx-EXT
T5HE-13-48P-8xx-EXT
T8-15-U6GC-8xx-EXT
ONLY USE THE CONTROL PROVIDED WITH OR SPECIFIED BY THESE INSTRUCTIONS TO CONTROL THIS LAMP. THIS LAMP WILL