RAB Lightcloud Controller Mini Скачать руководство пользователя страница 4

Contents 

 

Lightcloud Controller

Instruction Manual

Wire Nuts

Lock Nut

Gasket

x 3

x 3

POWER MEASUREMENT:

 The Lightcloud Controller is capable of

measuring the power usage of the attached circuit.

POWER LOSS DETECTION :

If mains power to the Controller is lost, 

the device will detect this and alert the Lightcloud application.

EMERGENCY DEFAULT:

 If communication is lost, the Controller may 

optionally fall back to a specific state, such as turning the attached 
circuit on.

Controller requires constant, unswitched power. Any wires not in use

must be capped off or otherwise insulated. This product should

only be installed by a qualified electrician and in compliance

with local and national electrical codes.  

!

 

 

Specifications

PART NUMBER

 

LCCONTROL/MINI

INPUT

 

120V-277VAC, 60Hz
<0.8W (Standby and Active)

 

MAXIMUM SWITCHED LOAD RATINGS

For Control of Electronic Ballast (LED)
and Magnetic Ballast
Electronic/Tungsten: 4.2A @120VAC
Inductive/Resistive: 4.2A @120VAC, 1.8A @277VAC 

OPERATING TEMPERATURE

-35ºC to +60ºC

OVERALL DIMENSIONS

 

1.6" diameter, 3.8" length  
1/2" NPT Mount, Male  

22AWG pigtails

18AWG pigtails

WIRELESS RANGE

 

 

Class 2  
IP66 Rated  
Indoor and Outdoor Rated
Wet and Damp Location
Plenum Rated

Line-of-Sight:    1000 feet
Obstructions:     100 feet

Содержание Lightcloud Controller Mini

Страница 1: ... RE HERE TO HELP 1 844 LIGHTCLOUD RAB Lighting Inc 170 Ludlow Avenue Northvale NJ 07647 Custom manufactured in China 1 844 544 4825 support lightcloud com Lightcloud is a commercial wireless lighting control system It s powerful and flexible yet easy to use and install Learn more at lightcloud com ...

Страница 2: ......

Страница 3: ...r television reception which can be determined by turning the equipment off and on the user is encouraged to try and correct the interference by one or more of the following measures Reorient or relocate the receiving antenna Increase the separation between the equipment and receiver Connect the equipment into an outlet on a circuit different from that to which the receiver is connected Consult th...

Страница 4: ... Any wires not in use must be capped off or otherwise insulated This product should only be installed by a qualified electrician and in compliance with local and national electrical codes Specifications PART NUMBER LCCONTROL MINI INPUT 120V 277VAC 60Hz 0 8W Standby and Active MAXIMUM SWITCHED LOAD RATINGS For Control of Electronic Ballast LED and Magnetic Ballast Electronic Tungsten 4 2A 120VAC In...

Страница 5: ...44 544 4825 support lightcloud com WE RE HERE TO HELP Functionality Configuration Operating Modes To configure Lightcloud products use the Web Application control lightcloud com or call 1 844 LIGHTCLOUD CONTROLLER Provides switching and dimming for a single zone REPEATER Extends the Lightcloud mesh network without controlling a load SENSOR REQUIRES OPTIONAL SENSOR MODULE Provides occupancy vacancy...

Страница 6: ... network Blinking RED when not connected The device will automatically continue trying to connect to a network in Setup Mode Illuminates when the device receives a message and blinks the signal strength 3 Blinks Best signal 2 Blinks Acceptable signal 1 Blinks Unacceptable signal Consult the Finding a Location section for more information STATUS INDICATOR SIGNAL INDICATOR Illuminated when device is...

Страница 7: ...m It s recommended that each device is scanned just before or just after being wired so no devices are missed The more notes that are given the easier it is to commission the system Send to RAB Once all of the devices have been added and organized submit the information for commissioning Device Table 3b For setup and maintenance we provide two Lightcloud Device Tables with the Gateway one that you...

Страница 8: ... Gray 0 10V common 2a Install at a Junction Box Indoor Outdoor 2b At Lighting Panel or Trough Space and code allowing you may install Lightcloud devices directly in your breaker box or lighting panel Alternatively break out lighting circuits and install Lightcloud devices in a separate trough Controller requires constant unswitched power When power switch is set to OFF Controller is disconnected f...

Отзывы: