9
Technical data
9.1
Electric cable size and fuses
Important
• The voltage on the compressor terminals must not deviate more than 10% of the
nominal voltage.
It is however highly recommended to keep the voltage drop over the supply cables
at nominal current below 5% of the nominal voltage (IEC 60204-1).
• If cables are grouped together with other power cables, it may be necessary to use
cables of a larger size than those calculated for the standard operating conditions.
• Use the original cable entry. See section
.
To preserve the protection degree of the electric cubicle and to protect its
components from dust from the environment, it is mandatory to use a proper
cable gland when connecting the supply cable to the compressor.
• Local regulations remain applicable if they are stricter than the values proposed
below.
• Currents are calculated with the full service factor, but we suggest to add 10% due
to over- and under-voltage. Fuses are maximum allowed values for full service
factor and 10% over- and under-voltage.
•
Caution
• Always double check the fuse size versus the calculated cable size. If
required, reduce the fuse size or enlarge the cable size
• Cable length should not exceed the maximum length according to IEC60204
table 10
Currents and fuses
IEC approval
Compressor specification
I(1)
Max Fuse
(1)
I(2)
Max Fuse
(2)
Type
gL/gG
gL/gG
V
Hz
A
A
A
A
A1
30kW
230
50
120
125
130
160
A2
30kW
230
50
120
125
130
160
X
30kW
230
50
120
125
-
-
A2
30kW
220
60
120
160
131
160
X
30kW
220
60
120
160
-
-
A1
30kW
230
60
117
125
128
160
X
30kW
230
60
117
125
-
-
A1
30kW
400
50
69
80
75
80
A2
30kW
400
50
69
80
75
80
X
30kW
400
50
69
80
-
-
A1
30kW
440
60
62
63
68
80
A2
30kW
440
60
62
63
68
80
X
30kW
440
60
62
63
-
-
Instruction book
2920 7101 24
89
Содержание QGS 90
Страница 2: ......
Страница 19: ...Electric cubicle Y D typical example Instruction book 2920 7101 24 17...
Страница 21: ...The drawings are on the USB supplied with your machine Instruction book 2920 7101 24 19...
Страница 132: ......
Страница 133: ......
Страница 134: ...No 2920 7101 24 2021 08 Printed in Belgium Performance You Demand Reliability You Trust www quincycompressor com...