8
StorNext G300 Specifications
G300 Gateway Appliance Site Planning Guide
Table 5 Cable Drops
Table 6 Power Requirements
Caution:
To safeguard continuous operations in the event of a power outage,
Quantum recommends that you connect the StorNext G300 gateway
appliance to a UPS (uninterruptable power supply). Two circuits should be
used (one per power supply).
Depth (front to back)
24.5 in (62.2 cm)
Weight (stand alone)
37 lbs (16.78 kg)
Rack Space Required
2U
Air clearance
Open 4 in (10.2 cm) behind unit for proper air flow
StorNext G300 Cable Drops
Ethernet Cable Drops
Gateway LAN Client direct Ethernet connections, Ethernet switch
connections, and Ethernet connections for SAN metadata.
Power Outlets
System
- 2 USA type 3-prong power outlets (
Nema 5-15
) or 2 C13 type
3-prong power outlets (
IEC320 C13
).
StorNext G300 Power Requirements
Power Supplies and Cords
Two (2) hot swappable redundant power supplies
Two (2) USA type 3-prong power cords with
IEC320 C13
to
Nema 5-15
connectors
Two (2) C13 to C14 type 3-prong power cords with
IEC320 C13
to
IEC320 C14
connectors
Input Voltage
100–240 VAC
Input Frequency
50–60Hz
Rated Current
10-5 amps
Maximum Operating Current
2.5-1.0 amps
Inrush Current
5.2-5.1 amps
Maximum Operating Wattage
242 watts
Maximum Operating BTUs
825 BTU/hr