ActiveScale™ OS X100 Rackless Installation Guide
106
8.1 About PDU requirements
In this step, mount the PDUs in the rack and connect the PDUs to power.
Note:
Do not plug any ActiveScale X100 components into the PDUs until the
step
Detailed technical requirements for PDUs are contained in
on page 245. However, as a
high-level summary, when evaluating PDUs for ActiveScale X100 consider the following requirements:
• PDUs should support 7kW (nominal) and 8.3kW (short term maximum) of power (North America,
Japan).
• Between all the PDUs, there should be at least 35 open receptacles for powering ActiveScale X100
components.
Work with your data center electrician to ensure that the power going to, and coming out of, the PDUs is
balanced.
As some ActiveScale X100 components draw significantly more power than others, it is important that
components be plugged into PDU receptacles in a way that provides redundancy and keeps the power load
balanced. However, for purposes of determining the placement of PDUs in the rack, be aware that power
cables from components installed in both the top and bottom of the rack will need to reach adjacent
receptacles in the same PDU.
8.2 Powering on the ActiveScale X100 components
If your system uses Quantum Corporation-supplied PDUs, it powers up in this order:
• System Interconnects
• Management Interconnect
• System Nodes
• Storage Enclosure Basics
• (After 1-2 minute delay) Storage Nodes
There is a delay in starting up the Storage Nodes to allow all the disks in the Storage Enclosure Basics to
spin up completely.
To power on the ActiveScale X100:
Содержание ActiveScale X100
Страница 1: ...ActiveScale X100 Rackless Instalation Guide 6 68841 03 Rev A with ActiveScale OS 6 0 2 software...
Страница 28: ...ActiveScale OS X100 Rackless Installation Guide 28...
Страница 34: ...ActiveScale OS X100 Rackless Installation Guide 34...
Страница 36: ...ActiveScale OS X100 Rackless Installation Guide 36 Assemble the remaining Storage Enclosure Basics on page 66...
Страница 59: ...ActiveScale OS X100 Rackless Installation Guide 59 Figure 3 14 Installing the I O module...
Страница 68: ...ActiveScale OS X100 Rackless Installation Guide 68...
Страница 76: ...ActiveScale OS X100 Rackless Installation Guide 76...
Страница 80: ...ActiveScale OS X100 Rackless Installation Guide 80 Figure 5 30 Rail attaching to front vertical rail...
Страница 91: ...ActiveScale OS X100 Rackless Installation Guide 91 Figure 6 36 Cabling Storage Node 4...
Страница 92: ...ActiveScale OS X100 Rackless Installation Guide 92 Figure 6 37 Cabling Storage Node 5...
Страница 94: ...ActiveScale OS X100 Rackless Installation Guide 94 Figure 6 39 Cabling System Node 1...
Страница 95: ...ActiveScale OS X100 Rackless Installation Guide 95 Figure 6 40 Cabling System Node 2...
Страница 98: ...ActiveScale OS X100 Rackless Installation Guide 98...
Страница 108: ...ActiveScale OS X100 Rackless Installation Guide 108...
Страница 110: ...ActiveScale OS X100 Rackless Installation Guide 110...
Страница 127: ...ActiveScale OS X100 Rackless Installation Guide 127 Figure 10 19 Post Login Storage Policy...
Страница 155: ...ActiveScale OS X100 Rackless Installation Guide 155 Figure 10 47 Post Login Durability Policy...
Страница 162: ...ActiveScale OS X100 Rackless Installation Guide 162...
Страница 234: ...ActiveScale OS X100 Rackless Installation Guide 234...
Страница 238: ...ActiveScale OS X100 Rackless Installation Guide 238...
Страница 240: ...ActiveScale OS X100 Rackless Installation Guide 240...
Страница 244: ...ActiveScale OS X100 Rackless Installation Guide 244...
Страница 260: ...ActiveScale OS X100 Rackless Installation Guide 260...
Страница 262: ...ActiveScale OS X100 Rackless Installation Guide 262 Figure 21 20 Components and port identification...
Страница 263: ...ActiveScale OS X100 Rackless Installation Guide 263 Figure 21 21 ActiveScale X100 cable wiring key...
Страница 264: ...ActiveScale OS X100 Rackless Installation Guide 264...