QUANTECH
9
Form QCC2-NM1
Issue Date: 5/20/2021
1
Section 1 – General equipment information and safety
Introduction
The 15 ton to 80 ton (50 kW to 280 kW) QCC2 models
are shipped complete from the factory ready for field
installation.
The unit is pressure-tested, evacuated and given a ni-
trogen holding charge and includes an initial oil charge
(R-410A refrigerant supplied by others). After assem-
bly, an operational test is performed to ensure that each
control device operates correctly.
The unit structure is heavy-gauge, galvanized steel.
This galvanized steel is coated with baked-on pow-
der paint which, when subjected to ASTM B117 1000
hour salt spray testing, yields a minimum ASTM 1654
rating of “6”. Units are designed in accordance with
NFPA 70 (National Elec tric Code), ASHRAE/ANSI 15
Safety code for mechanical refrigeration, and are cETL
listed. All units are produced at an ISO 9000-registered
facility.
Compressors
The condensing unit has suction-gas cooled, hermet-
ic, scroll com pressors. The compressors incorporate
a compliant scroll design in both the axial and radial
direction. All rotating parts of the compressors are
statically and dynamically balanced. A large internal
volume and oil reservoir pro vides greater liquid toler-
ance. Compressor crankcase heaters are also included
for extra protection against liquid migration.
Condenser
Coils
Fin and tube condenser coils of seamless, inter nally-
enhanced, high-condensing-coefficient, corrosion re-
sistant copper tubes are arranged in staggered rows,
mechanically expanded into aluminum fins. Integral
subcooling is included. The design working pressure
of the coil is 650 psig (45 barg).
Low sound fans
The condenser fans are composed of corrosion resis-
tant aluminum hub and composite blades molded into
a low noise airfoil section. They are designed for maxi-
mum efficiency and are statically and dynamically bal-
anced for vibration-free operation. They are directly
driven, and positioned for vertical air discharge. The
fan guards are constructed of heavy-gauge, rust-resis-
tant, PVC (polyvinyl chloride)-coated steel wire.
Motors
The fan motors are Totally Enclosed Air-Over, squirrel-
cage type, current protected. They feature ball bearings
that are double-sealed and permanently lubri cated.
Refrigerant circuit
All unit piping will be copper with brazed joints. The
liquid line will include a field connection shutoff valve
with charg ing port located on each condenser circuit.
Suction line connections are provided on each refrig-
eration circuit. A filter drier and sight glass are shipped
loose for field installation on each refrigerant circuit.
All expansion valves, liquid line solenoid valves,
refriger ant, and refrigerant field piping are supplied by
others.
Warranty
Quantech warrants all equipment and materials against
defects in workmanship and materials for a period of
eighteen months from date of shipment, unless labor
or extended warranty has been purchased as part of the
contract.
The warranty is limited to parts only replacement and
shipping of any faulty part, or sub-assembly, which has
failed due to poor quality or manufacturing errors. All
claims must be supported by evidence that the failure
has occurred within the warranty period, and that the
unit has been operated within the designed parameters
specified.
All warranty claims must specify the unit model, serial
number, order number and run hours/starts. Model and
serial number information is printed on the unit identi-
fication plate.
The unit warranty will be void if any modification to
the unit is carried out without written approval from
Quantech.
For warranty purposes, the following conditions must
be satisfied:
• The initial start of the unit must be carried out by
trained personnel from an Authorized Quantech
Service Representative
(see SECTION 6 – COM-
• Only genuine QUANTECH approved spare parts,
oils, coolants, and refrigerants must be used.
Содержание QCC2015CEE
Страница 12: ...QUANTECH 12 Form QCC2 NM1 Issue Date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 38: ...QUANTECH 38 Form QCC2 NM1 Issue Date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 46: ...QUANTECH 46 Form QCC2 NM1 Issue Date 5 20 2021 Section 5 Technical data THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 102: ...QUANTECH 102 Form QCC2 NM1 Issue Date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 152: ...QUANTECH 152 Form QCC2 NM1 Issue Date 5 20 2021 THIS PAGE IS INTENTIONALLY LEFT BLANK...
Страница 171: ...QUANTECH 171 Form QCC2 NM1 Issue Date 5 20 2021 Notes...