Advanced Calculation Setup Method
This method allows you to configure the advanced scaling parameters for input module
types that are set to “CT, Temperature.” The advanced calculation method is capable of
adapting the winding temperature model for all the different stages of cooling, thereby giving
a more accurate response than the Simple Calculation Method. But to use this method, the
winding rise parameters are required for each cooling stage. The formulas for calculating
winding temperatures for this window were derived from the IEEE Std C57.91-1995.
The
Advanced CT Temperature Scaling Setup
window opens when you click [Advanced
Input Module Setup
window.
More Information
•
The Importance of Winding Temperature and Cooling
•
•
Advanced Winding Rise Parameters
•