A. Mantel and Wall Projections
WARNING! Risk of Fire!
Comply with all minimum clear-
ances to combustibles as speci
fi
ed. Framing or
fi
nishing
material closer than the minimums listed must be construct-
ed entirely of noncombustible materials (i.e., steel studs,
concrete board, etc).
Clearance to combustible material under the insert is 1/4
inch (6 mm). Clearance from top of
fi
replace opening for
combustibles extending 12 inches max. is 12 inches.
• Use leveling legs to raise insert minimum 1/4 inch (6 mm)
above combustible material or outer wrap of factory built
fi
rebox.
Combustible facings must not extend behind the insert
surround. For non-combustible material speci
fi
cations
refer to section 1.E.
11
11
Finishing
EXISTING NON-COMBUSTIBLE FACING
12 IN.
MAX.
12 IN. MIN.
2 IN.
MAX.
10 IN. MIN.
Figure 11.1 Mantel Clearance
B. Remove the Shipping Materials
Remove shipping materials from inside or underneath the
fi
rebox. Remove metal panels covering electrical compo-
nents on sides of appliance.
C. Inspect Firebox
Surface cracking or crazing of
fi
rebrick material is normal
and expected. All cracks are acceptable and do not require
replacement of the unit or the
fi
rebox with the exception of:
• Cracks compromising the surface plane of the
fi
rebox.
See Figure 11.5.